Download Avanta_Plus_C&S_Installation
Transcript
Remeha Avanta Plus 2. Installation Terminal Block X2 5 N 4 L 3 Exist links 2 1 Power supply to external time clock -230v Switch live (230v) from external time clock DHW demand Remove existing link 4-3 to use this function Switch live (230v) from external time clock HTG demand Remove existing link 4-1 to use this function X2 Terminal Block X5 1 Neutral 2 Open valve to DHW (230v) 3 Open valve to HTG (230v) For external DHW priority diverting valve on System boiler when used in conjunction with "Open Therm" compensation Terminal Block X6 X5 X6 X7 X9 230v - 3 Amp Power Supply L N Terminal Block X7 1 2 3 E Common Alarm Boiler Run or (Closes on alarm) external pump relay (Closes on run) Terminal Block X9 1 2 3 4 Exist links 5 6 7 8 Outside sensor (red band) for direct boiler weather compensation or when used in conjuction with a compatable Open Therm control eg: Chronotherm or iSense DHW sensor (red band) or volt free thermostat (make on temp fall) Remove existing link to use this function External interlock (volt free) Serial function with water pressure switch Modulating - using Open Therm control eg: Honeywell Chronotherm or iSense On / Off - using volt free switching control eg: Celcia 10 or low volt room thermostat NOTE: Terminal blocks are not in line as shown - diagramatic only fig. 21 Boiler External Connection terminal details R000151-B R000151-B 127768-271011 21