Download Avanta_Plus_C&S_Installation
Transcript
4. Errors Remeha Avanta Plus Error code Description e11 Air box tempera- Air leakage from heat ture to high exchanger to air box e13 Heat-exchanger Heat exchanger faulty. fuse protection has responded; Insufficient water. replace the heat exchanger after No through flow. finding and solving the cause. e43 Parameter limits Automation settings Replace df / dV settings, see par. 2.9.10 If this error code still returns after resetting; please contact Remeha. e44 Parameter check Automation settings Replace df / dV settings, see par. 2.9.10 If this error code still returns after resetting; please contact Remeha. e45 Default parameters Replace boiler control unit. Possible cause Check / solution Check: • The sealing of the viewing glass; • Whether front plate of heat exchanger is properly tightened • Front plate sealing; • Whether ignition electrode is properly fitted Check wiring between heat exchanger fuse. Check the minimum water pressure, read off the gauge and check for leaks. Check that the pump is working; turn the spindle with a screwdriver, if that works but the pump still does not respond, check the wiring; that is in order the pump is faulty. Automation settings table 13 Error codes * When sensors have been taken out, be sure to replace them max. 40 mm underneath heat exchanger. If you read out a not listed error, please report to Remeha. Temperature/resistance diagram 25000 resistance in Ω 20000 15000 10000 5000 0 10 20 30 40 50 60 temperature in °C fig. 64 Sensor resistance graph Sensor resistance 70 80 90 100 4.3 Control stop or lock-out The code K8 , K5 or K9 can appear in the display. • Code K8 is a control stop and will appear if the measured flow temperature (t1) is higher than the flow temperature set (Tset flow). The boiler will start working again automatically once the flow temperature falls below the flow temperature set. • Code K5 is a control stop from 3 till 10 minutes and appears if the set flow temperature (t1) has already been reached and the heating demand still exists. • Code K9 is a shut down and appears if the maximum temperature rise is exceeded or if the ΔT between the supply and return temperature ≥ 45°C or a rate of rise in the flow temperature > 1°C/sec. And also at a boiler-start with no through flow or insufficient water. The boiler will try to restart after 10 minutes. • Code K9 is a shut down and can appear in the following situation: - The lock-out down input (between connectors 5 and 6 on terminal block X9) has been activated (= opened). The shut down will disappear once the cause has been removed! 54 127768-271011