4. Errors
Remeha Avanta Plus
Error
code
Description
e11
Air box tempera- Air leakage from heat
ture to high
exchanger to air box
e13
Heat-exchanger Heat exchanger faulty.
fuse protection
has responded; Insufficient water.
replace the heat
exchanger after No through flow.
finding and solving the cause.
e43
Parameter limits
Automation settings
Replace df / dV settings, see par. 2.9.10
If this error code still returns after resetting; please contact Remeha.
e44
Parameter check Automation settings
Replace df / dV settings, see par. 2.9.10
If this error code still returns after resetting; please contact Remeha.
e45
Default parameters
Replace boiler control unit.
Possible cause
Check / solution
Check:
• The sealing of the viewing glass;
• Whether front plate of heat exchanger is properly tightened
• Front plate sealing;
• Whether ignition electrode is properly fitted
Check wiring between heat exchanger fuse.
Check the minimum water pressure, read off the gauge and check
for leaks.
Check that the pump is working; turn the spindle with a screwdriver,
if that works but the pump still does not respond, check the wiring;
that is in order the pump is faulty.
Automation settings
table 13 Error codes
* When sensors have been taken out, be sure to replace them max. 40 mm underneath heat exchanger.
If you read out a not listed error, please report to Remeha.
Temperature/resistance diagram
25000
resistance in Ω
20000
15000
10000
5000
0
10
20
30
40
50
60
temperature in °C
fig. 64
Sensor resistance graph
Sensor resistance
70
80
90
100
4.3
Control stop or lock-out
The code K8 , K5 or K9 can appear in the display.
• Code K8 is a control stop and will appear if the measured
flow temperature (t1) is higher than the flow temperature
set (Tset flow). The boiler will start working again automatically once the flow temperature falls below the flow temperature
set.
• Code K5 is a control stop from 3 till 10 minutes and
appears if the set flow temperature (t1) has already been
reached and the heating demand still exists.
• Code K9 is a shut down and appears if the maximum
temperature rise is exceeded or if the ΔT between the supply and return temperature ≥ 45°C or a rate of rise in the
flow temperature > 1°C/sec. And also at a boiler-start with
no through flow or insufficient water. The boiler will try to
restart after 10 minutes.
• Code K9 is a shut down and can appear in the following
situation:
- The lock-out down input (between connectors 5 and 6 on
terminal block X9) has been activated (= opened).

The shut down will disappear once the cause has been
removed!