Connect one end of each cable shield to GROUND at the generator set. GND Generator Set RBUS 12 VDC A A B B PWR PWR COM COM Connect shields together as shown. 1 RXT 4 3 TB1 A A B B PWR PWR COM COM Generator Set Terminal Block TB1. See Figure 1-6 for location. Check the decal on the generator set for terminal block connections. PIM A A B B PWR PWR COM COM A B PWR LCM COM Note: See Figure 1-21 for maximum total cable length per run (1 run shown). Leave one end of each cable shield disconnected at the last device. 1. Communication cable Belden #9402 or equivalent 20 AWG shielded, twisted-pair cable Figure 1-22 Accessory Module Communication Connection Details TP-6803 12/11 Section 1 Installation 25