Download Manual for DX4102
Transcript
SOLAR SYSTEM REGULATOR DX 4102.G User manual May 2007 A0650_1.odt 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. Content 1. INTRODUCTION..........................................................................................................................3 2. CONTROL FUNDAMENTALS...................................................................................................4 2.1 REGULATION FUNDAMENTALS............................................................................................................4 2.2 PUMP PERFORMANCE REGULATION......................................................................................................4 2.3 COLLECTOR TEMPERATURE SENSING...................................................................................................6 2.4 COLLECTOR OVERHEATING................................................................................................................6 2.5 AUXILIARY OUTPUT.........................................................................................................................6 2.6 SUBSIDIARY ENERGY SOURCE............................................................................................................6 2.7 SECONDARY LOOP PUMP...................................................................................................................7 2.8 REGULATION FAILURES BEHAVIOUR....................................................................................................7 2.9 ENERGY MEASURING........................................................................................................................7 3. SERVICE MANUAL.....................................................................................................................8 3.1 DEVICE DESCRIPTION.......................................................................................................................8 3.2 MENU STRUCTURE...........................................................................................................................9 Menu items...............................................................................................................................9 Service setting.........................................................................................................................10 3.3 REGULATION STATUS DISPLAY.........................................................................................................13 Regulation status....................................................................................................................13 Loop and collector temperatures...........................................................................................13 Energy and power given by collector panels.........................................................................14 3.4 FAILURE WARNING.........................................................................................................................14 4. INSTALLATION DIRECTIONS...............................................................................................15 4.1 DEVICE DIMENSIONS......................................................................................................................15 4.2 WIRE CONNECTIONS.......................................................................................................................16 4.3 INSTALLATION INSTRUCTIONS...........................................................................................................17 4.4 PC CONNECTIONS..........................................................................................................................17 5. TECHNICAL DATA....................................................................................................................20 A0650_1.odt 2 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 1. Introduction Regulator DX4102 (in next text regulator or device) is determined to regulation system consists of solar collectors and a warm exchanger to gain warm energy and propagate it to the other systems. Warm exchanger could be for example boiler, water basin or central heating system. Regulator distributes warm carrying fluid to warm exchanger using actuator (pump) according to set up temperature. Device is equipped with timing facilities (programmable), which could use subsidiary energy source (electric heating alternatively gas kettle-drum), providing heat limitations in loop. Alternatively device can control secondary loop pump with time delay function. Device is able to count up the energy given to warm exchanger. DX4102.G behavior can be set up according to requested system parameters - "programming", Programming uses four keys and Liquid Crystal Display (LCD) located at front panel of the device. There can be found Light Emitting Diodes for power supply indication, system failure. Regulator is equipped with current loop for data communication with Personal Computer. Software named “EkoSolar” allow user to watch, modify and archive all important data and solar system parameters. A0650_1.odt 3 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 2. Control fundamentals 2.1 Regulation fundamentals Regulator is one-loop (one-channel) differential regulator. Controlled system consists of solar collectors, heat exchanger (A) and actuator, which distribute warm liquid to exchanger. Regulator in a forever cycle watches temperatures at the exchanger and compares it with the requested values. To pump warm liquid to exchanger two conditions must be fulfilled (in next text abbreviated start pump conditions): 1. Insufficient heat exchanger temperature - measured exchanger temperature must be lower than requested temperature (see "Menu-Temp"), set hysteresis 1 K. 2. Sufficient collector energy - collector temperature must be higher over minimum difference "DeltaON" (see "Menu-Delta") than exchanger temperature to start pump. Pump stops if difference falls below "DeltaOFF" - see 2.1. Parameter "Delta" is needed because of thermal loss in piping between collector and exchanger. T [°C] Tcol DeltaON DeltaOFF sufficient energy Tex t [sec] Fig.1 Pump condition – sufficient collector energy In case the pump conditions are fulfilled (exchanger has insufficient temperature and in collector has sufficient energy), the loop will be switched on e.g. warm liquid will be pumped through this loop. In case the loop has not fulfilled conditions for loading warm, pump stops. Providing the loop have defined subsidiary energy source ("Menu-Service-Aux.Out=Heating") and exchanger have insufficient temperature, but collector will not have sufficient energy for this loop, it will be enabled subsidiary heating (see chap 2.6), that is time and temperature dependent. 2.2 Pump performance regulation Device can control the pump performance with pulse-width modulation – to decrease performance the pump is switched of for some tens of milliseconds. Performance regulation is enabled if "Menu-Service-PWMmod" is set up less than 100% (minimal 20%). Pump performance is controlled (see chap. 2.2) if temperature sinks (collector to exchanger) below DeltaON level. The performance is decreased to Pmin till an average value of DeltaON and DeltaOFF, than it stays on Pmin till difference falls below DeltaOFF A0650_1.odt 4 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. Exchanger A Sk Sh Collector T P1 F EH Sa Sx Sensors (temperature): Sk-collector, Sh-subsidiary heating, Sx-return fluid , Sa – exchanger , F- flow meter Actuator: EH – electrical heating element, P1 – pump; T - solar fluid tank Fig.2 Block scheme of regulated system including subsidiary heating Sk Exchanger A Collector Sa T P1 F Sx P2 Sensors (temperature): Sk-collector, Sa – exchanger, Sx-return fluid , F- pulse flow meter Actuator: EH – P1 – pump, P2 – secondary loop pump, T - solar fluid tank Fig.3 Block scheme of regulated system with secondary loop pump Tcol T [°C] Tex + DeltaON Tex + DeltaOFF t [sec] OFF maximal speed OFF PWM band – slow down speed to Pmin PWM band – Pmin speed Fig.4 PWM band display – pump performance regulation A0650_1.odt 5 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 2.3 Collector temperature sensing Collector temperature sensing is made by fixing collector sensor to collector corpus (see menu Service-Sensor) and collector loop is "drain-back" type ("Sensor=Drain"). Drain-back system – is created of collector loop with FILL-in and FILL-out liquid (using solar fluid tank) after an activation condition is fulfilled (collector temperature is over "DeltaT" value greater than exchanger temperature). If it is true the pump is started for defined time A at full power (the liquid is transported to collector fields), then the power is slowed down (necessary to keep the flow level) for fixed interval B to get system niveau. In the end the collector loop is set to normal process. After the finishing, (loading condition is false), the warm liquid is filled out from the loop to fluid tank. 2.4 Collector overheating If exchanger is full loaded (has enough energy) and the sun shines it could happen collector overheating. That is why regulator is equipped with „overheating protection“ which can be activated in menu (see chap. 3.2). As the collector temperature increases over 105 °C the primary pump start running till the exchanger temperature reaches MaxTexc (see menu Service) or collector temperature sinks below 100 °C. The overheating check stops if collector temperature increases over 120 °C and will be started again if collector temperature falls below MaxTexc. This is reasonable if the power (230V) is missing for some time (power failure). 2.5 Auxiliary output Device is equipped with special output (X/Y), which can be used for cooperation with exchanger or like standalone timer output. In case of exchanger the auxiliary output is used for: 1. subsidiary heating (see chap. 2.6) 2. secondary pump management (see chap. 2.7) Stand alone timer output - non periodic timer – time window are give by table ( see "MenuTimer"). When configuring use of auxiliary output (see Servis – chap. 3.2) firstly the exchanger is chosen then the way of its using (heating, secondary pump) and after the necessary parameters are set. 2.6 Subsidiary energy source Device is equipped with time functions ("Menu-Timer"), which is used to rank auxiliary (subsidiary) energy source (electrical heating or gas kettle) for insufficient exchanger heat ("MenuService-Aux.Out=A-Aux.Out=Heating"). Auxiliary heating will be activated if (all conditions must be fulfilled): 3. the time window condition is true, see menu "Timer" 4. the exchanger temp. is lower than start temp. (see "Servis-Aux.Out-...-Temp ON") 5. the exchanger (that with auxiliary heating) is not just being selected for warm loading Auxiliary heating will be switched off, if some of conditions 1. and 3. is false, or the exchanger temperature is higher than stop temperature (see "Servis-Aux.Out-...-Temp OFF"). There is left a possibility to sense temperature in exchanger with another sensor which is fixed in top of exchanger height - see example in Fig. 2 sensor Sh). Physically sensor is connected to S4 position.(see chap 4.2). This function will be activated automatically if sensor is present. Aux.Out='–', then output XY will be controlled according to item "Timer", it means it is not bound to loop conditions. Auxiliary energy source will be automatically switched off at High Tariff (energy cost is expensive), if the digital input is set to "Hi.Tarif" (viď "Service-Typ Inp"=" Hi.Tarif ") and corresponding digital input is shorted. A0650_1.odt 6 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 2.7 Secondary loop pump Regulator is able to use a secondary loop pump for a exchanger "Menu-ServiceAux.Out=Sec.Pump". If this is true then this output is is controlled together with corresponding primary loop and it is stopped with preset time delay "Menu-Service-Aux.Out-...-PostPump". Providing that exchanger sensor is localized at the pipe of secondary loop, the measured temperature is real only for fluid circulating. That is why the regulator manages temperature check function "Service-Aux.Out-...-CheckTem", where the regulator starts fluid pumping in a given period "Service-Aux.Out-...-CheckTem-per", for a given interval "Service-Aux.Out-.. CheckTem- on", and it is enabled only if "sunshine" is set up (see chap.2.3 2.8 Regulation failures behaviour If the sensor failure is found regulator behaves in a following way: ● Collector sensor failure – warm liquid does not stop running (till the fault removing) Exchanger sensor failure – the warm carrying fluid is pumped out till sensor malfunction is removed, but only if collector temperature is higher than 60°C ● Subsidiary sensor failure (S4) – subsidiary heating takes as reference value exchanger sensor value (S2) ● Return fluid sensor failure – temperature difference will be set 0 K, it means no instant power (a energy will not be accumulated). ● 2.9 Energy measuring Regulator can calculate the energy gained from collector. Energy is counted according the formula: Q= c. m. dT, where c is relative warm capacity, m is mass and dT is temperature difference warm carrying fluid (market name Solaren). Fluid mass is evaluated as m= q. V, where V is volume and q is pumped fluid density (the value is temperature dependent). The volume is either measured by flow-meter (see chap. 3.2) either counted out from time of fluid flow and given flow per a minute. The temperature difference is given like collector to exchanger output temperature (return fluid sensor needed) or it is fixed difference set by DiffTemp (see chap.3.2). For the second case the measuring is for informative purpose only. Relative warm capacity and fluid density is assumed for SOLAREN (non diluted) ! Energy is counted up as cumulative number increasing for each period. Counter can be cleared manually by user see “Service-Energy-Clear Ac” or “Records-Counter-date nul”. After reaching 10000 kWh it is cleared in automatic way. Day registers (32 days backward) - keep energy for each day. The records can be seen in “Records” menu (chap.3.2). Instant collector power represents (gained) energy amount per fixed period. Periode is given as the delay between two flow-meter pulses or is set fixed one minute. A0650_1.odt 7 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 3. Service manual 3.1 Device description Regulator consists of (seen from the front panel) LCD display (two rows per 8 characters), a four key keyboard (KBD) and LED indicators (PWR a ERR), see Fig. 6 With display and keys user can get an information about regulation status, find out measured and requested values or edit parameters and so on. Parameter accessing is realized by menu structure. Fig.5 Regulator front panel Keyboard is represented with a group of four keys. The meaning of keys follows: F ...Function key – quit without change for editing (Escape) a return to upper level E ...Enter – confirmation for editing value (Enter) – stores value and moves to next item ▲...menu items change in defined direction, press = +1, hold dynamic value increasing ▼...menu items change in defined direction, press = +1, hold dynamic value increasing ▲,▼ at the same time pressed – setting up minimal value for selected parameter Two light indicators signalize: PWR – power supply presence ERR - system failure (ERR flashes) – sensor or internal regulator failure see chap. 3.4 A0650_1.odt 8 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. The processed values can be seen in two display windows. Window change involves "E" key see 3.1, window description can be found in chap.3.3. Pressing "F" key enables menu display for requested regulation parameters, date, time and service parameters. Detail menu description covers chap 3.2. Regulation status Collector, exchanger temperatures Gained energy instant collector power 11:25 /B 08-03 E F menu E F K 82 X65 A39 R45 Menu Service E F 1234.56k 003.21kW Fig.6 Regulation status versus menu 3.2 Menu structure Menu is involved by pressing "F" key if regulation process display is active. Menu items can be selected by ▲,▼ items, confirmation enables "E" key, current level quits "F" key. Changed item is flashing. After reaching the maximal value the minimal is set and vice versa. Menu items ♦ Date date setting. Firstly day in a month, then month an in the end the year. If date is set incorrect (30.02.2004) cursor (_) returns back to day of month position. ♦ Time time setting. First is set summer (S) / winter (W) time then hours and minutes in the end. Choosing summer or winter involves time the hours are set up automatically. ♦ Timer timer setting - maximal 8 time interval during a day (00:00-23:59). First time to switch on , then switch off (value 24:00 represents switch off at 00:00). ♦ Records day gained energy records (see Fig.9) Counter shows cumulated energy (from time of last clearing) Energ.QH gained energy corresponding to last quarter of an hour Energ. D gained energy for last 32 days (each day individually) ♦ Manual manual setting outputs of regulator – three modes: "Aut" = controlled by regulation algorithm, "ON" – always ON, "OFF" – always OFF ♦ Delta setting start and stop difference for exchangers (Kelvin values). Start difference DeltaON is minimal temperature difference (collector to exchanger temperature) to start pump running. Stop difference DeltaOFF minimal value to stop pump. ♦ Temp exchanger requested value (ºC) ♦ Service service parameters setting A0650_1.odt 9 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. Main menu Vertical moving: ↑↓, Horizontal moving: E Menu E Menu Date Date setting E Timer #1 06:30 auxiliary heating timer Menu Records E Date 27.07.02 Month Year E Time S 11:30 S-summer time W-winter time Time setting Menu Timer E Time S 11:30 E Date 27.07.02 Day in a month E Menu Time E Date 27.07.02 Time S 11:30 Hours Minutes next interval (max.#8) Edit interval number E Timer #1 06:30 Hour to start E Timer #1 10:00 Minute to start Timer #1 10:00 E Hour to stop Minute to stop Processed energy records (log) - see menu Records Output name Menu Manual E Manual PN= AUT manual output set up Menu Delta E E AUT= automat, ON- always on, OFF - always off Delta[K] A 10 02 E Service menu E Delta[K] A 10 02 starting difference stopping difference Temp A= 60°C Exchanger A temperature Exchanger requested value Menu Service next outputs Exchanger A Collector to exchanger difference Menu Temp E Service 0715 E Service 0715 day in a set month E Service xxxxxxx current hour see Service menu Access password Fig.7 Regulator menu Service setting Service menu access is protected by knowledge of code. Service settings should be set at beginning (first installation) that is why the password is "ddhh" needed (dd day in a set month and hh hour set in device). Service menu items:: ♦ Sensor collector sensor localization (see chap.2.3). There are two possibilities: ➢ Drain at collector corpus (see chap. 2.3) • Delta T temperature difference • Time A power maximal (fill in) time • Time B power minimal (stabilize flow) time ♦ Prot.Col collector overheating protection (Enable=Yes, Disable= No). If enabled next parameter appears MaxTec. ♦ Aux.Out auxiliary output XY definition. Firstly must be defined exchanger (if none XY output will be by "Timer" variable controlled), then the purpose must be defined: heating (see 2.6) or secondary loop pump (see 2.7). For heating the start and stop times are set, for secondary pump off time delay and pipe sensing items (similar to collector pipe) see "Sensor- Pipe" ♦ PWMmod actuator pump performance (see chap. 2.2) for A loop (20-100%). 100% means full pump speed. ♦ ParEnerg parameters for gained energy from collector panels (see 3.2): A0650_1.odt 10 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. ➢ Flow flow meter setting – if pulse flow meter is used (Flow imp=Yes), flow is set up in liters / pulse, if no flow meter is used then in liters / pulse. ➢ BackTemp return fluid sensor using (No/Yes = used), for no sensor it is recommended set up temperature difference of collector (between output and input). ➢ Clear Ac clears gained energy counter (accumulator)tupom). ♦ Com.par serial line communication parameters: address and baud rate ➢ adr device address (0-19). Important for more regulators at the line, otherwise 0. ➢ S baud rate (1200, 2400, 4800 or 9600 Baud) ♦ Mode I/O input / output parameters ➢ Inv.Out. output: Direct ("Norm") or inverted ("Inve"). If inverted and it is a demand to switch on, the output will be switch off and vice versa. ➢ Inv.Inp. digital inputs D1 and D2 ("Norm"/"Inve") – if NORM active for short, otherwise active for open circuit ➢ Using D2 Digital input D2: "no use" – free, "Sunshine" – extern light intensity sensor, "Hi.Tarif" – disable electrical heating if High tariff signal appears menu Records Records Records Counter Vertical move: ↑↓, Horizontal move: E E A= [kWh] 1234.67 date nul 20.04.05 Gained energy counter Gained energy value (after 10000.00kWh> 0 .0 kWh) Energy value clearing menu E Clear No ? Clear Yes ? E Date of last clearing Accept clearing Backward day number(0 - current day) Backward date Records Energ. D E 00 25.04 123.5kWh Gainned energy of selected day Day energy registers Records Energ.QH E Backward day change (0-99) 00 12:45 12.35kWh Quarter of an hour registers E A quarter of an hour change (from 00:00 to current time) Next day in backward direction Amount of energy per given quarter Fig.8 Menu Records A0650_1.odt 11 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. menu Service Service Service Sensor Vertical move: ↑↓, horizontal move: E E E Sensor Drain work mode collector sensor position and mode Service Prot.Col E Prot.Col No Service Aux.Out E Yes Aux.Out A E Service ParEnerg Service Com.par. 65 E Aux.Out Sec.Pump 05 Aux.Out Timer (20-100%) E E E Mode I/O Inv.Out. E Output modes Mode I/O Using D2 E ON °C min Yes E E per15min on030sec time of temperature sensing at pipe (10-200 second) Com.par. S=9600Bd Baud rate Inv.Inp. D1=Norm E Inv.Out. PN=Norm next input modes Output modes: - Norm - direct - Inver - invert Input name Input modes 55 temperature sensing period (5,10,15,20,30 minutes) 1) device line address Mode I/O Inv.Inp. °C per15min on030sec Aux. output as timer Com.par Adr=00 °C pump stop delay (0-30 min) see menu "ParEnerg" E Time B 060 sec Temp. checking if sensor is fixed at pipe E PostPump CheckTem auxiliary output = secondary pump PWMmod A min=100% PC communication parameters Service Mode I/O E Aux.Out Heating auxiliary output = heating PWM pump performance E Start temperature(0-99 °C) (must be lower than stop) E Temp OFF Temp Stop temperature (0-99 °C) loop designed for subsidiary output : –,A E 95 Enabled auxiliary output using Service PWMmod Time A 060 sec stabilise time FILL-in time Max. warm exchanger minimal gradient to START temp.at collector pannel E Prot.Col MaxT.exc protection Disabled Overheating enabled E Delta T 15 K E next output modes Output name indikátor vysokého tarifu Using D2 no use not used digital input modes Using D2 Sunshine Using D2 Hi.Tarif light intensity sensor Fig.9 Menu Service A0650_1.odt 12 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. menu Energy Vertical move: ↑↓, horizonatal move: E ParEnerg Flow measuring parameters ParEnerg Flow E E Flow imp=No Flow 01.00l/m No flow meter used E Flow imp=Yes ParEnerg BackTemp E BackTemp sens=Yes Return flow sensor using ParEnerg Clear Ac E Flow (X.00-X.99 liter per min E Flow 01.00l/i Flow (X.00-X.99 liter pre pulse) Flow (0-99 liter pre pulse) BackTemp sens=No Used Flow 01.00l/m Flow (0-99 liter per min) Flow 01.00l/i Pulse flow meter used E E DiffTemp 10 °C Not used Return flow semnsor not used (estimated collector difference) (0-99°C) Clear Ac Yes Energy accumulator clearing Acknowledgement Fig.10 Menu Energy 3.3 Regulation status display Regulation status The upper line displays: time and loop activity – if loop works, the rotating icons and the name of the exchanger (A) and the flashing character representing non standard warm pumping: 'p'- the pipe temperature sensing (sensor at the pipe), 'e' – sensor failure, 'H' – collector overheating. The lower line displays: date and the character representing X output status ('E', auxiliary energy source, 'S', secondary loop pump, 'T', only timer), and failure report, if any happened. Flashing character - the reason for pump to run: 'e' – sensor failure 'H' – collector overheating 'z' - start FILL- in 's' - keep the flow 'w' – wait for temperature difference 'b' - blok fluid flow Rotating pump icon Time 11:25p×A 16-09T!! Date 'E' – auxiliary heating active 'S' – secondary loop pump active 'T' – timer active Active loop indicator Failure (flashing alternate with !!): HW - device SN - sensor MU - manual mode Fig.11 Regulator status If system detects a failure, the double „!!“ alternates flashing with code of the failure.: HWhardware error, SN – sensor error, MU – manual mode. Loop and collector temperatures The first line displays collector temperature, the lower one exchanger temperature. If the return fluid sensor is used, its temperature appears too. A0650_1.odt 13 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. For short circuit sensor flashing 'x' appears, for open sensor circuit '-' appears and if the temperature is less or greater then display width then flashing '9' appear. Collector temperature Return fluid temp K102 X70 A39 H45 Exchanger A temperature Auxiliary heating temperature Fig.12 Temperatures display Energy and power given by collector panels Upper line displays energy (kWh) propagated from collector from last clear (see Records). Lower line keeps instant power (kW) of collector panels. (see 3.3). Gain energy from collector [kWh] accumulated from last clear 1234.56k 003.21kW Instant gained power Fig.13 Energy and power of collector panel Through pressing the arrow keys (at keyboard), next window appear. There can be seen temperature difference and computed value of flow converted to minutes (liters per minute). Temperature difference collector – return pipe 34.6°C 12.34l/m Current flow value Fig.14 Temperature difference and flow value 3.4 Failure warning If some failure happened, the ERR light start to flash and display shows the error code (see chap.3.3). There are two main failures - system failure, sensor failure: 1. Sensor failure: instead of temperature value the "–" (open circuit sensor), "x" (short circuit sensor) or "?" (Analog to Digital Converter failure) character flash. The error code "SN" flashes. 2. System failure: ADC failure instead of temperature "?" flashes, Real Time Clock failure instead of time and date "?" appear. The error code "HW" flashes. 3. Manual mode: if some output should be switch on and it is not possible because of manual switch position, regulator shows flashing "MU" to annotate user. A0650_1.odt 14 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 4. Installation directions 4.1 Device dimensions Device is fixed at wall through metal console, that must be first installed. Regulator is manufactured in form of plastic box (125x83x35), that fixes at mentioned console.. Fig.15 Device dimensions A0650_1.odt 15 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 4.2 Wire connections Regulating system consists of: regulator, sensors and actuators (pumps). Sensors and actuators are connected to installation bracket, localized under the cover of the device.. Wiring diagram is given in. 10. fuse 8. 9. P+ P- S3 AG S4 AG L N P N 1. 2. X Y D1 DG D2 S1 AG S2 AG 3. 4. 5. 6. 7. Fig.16 Wiring diagram 1. power supply 230V~ (1) 2. output PN (2) – pump 3. potential- free output X / Y (3) – auxiliary output (4) 4. D1 digital input – pulse flow meter 5. D2 digital input - not used, High Tariff ("HiTariff"), sunshine ("Sunshine") 6. S1 collector temperature sensor 7. S2 warm exchanger temperature sensor 8. S3 return flow temperature sensor 9. S4 sensor for auxiliary output 10. P+, Pcommunication line PC (current loop 20mA) Notes: 1) The current flowing in this wire goes through fuse to PN output. !! Warning for the current value which is limited by fuse. Power actuators should be connected using additional relays or power relays! 2) As switching element used triac, power output 230V AC, maximal 1A 3) Relay contacts, 230V AC, 30V DC. Current limited to 1A - directly may be used load with dissipation max 230W (@ 230V~), if more power is required an additional relay or power relay must be used! 4) Auxiliary output may be used for: additional heating or secondary circuit pump or timer only X D1 DG Y L N P a) P(ump) output +5V D2 N b) X / Y output c) digital inputs D1, D2 Fig.17 Input - output equivalent connections A0650_1.odt 16 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 4.3 Installation instructions An installation of the device should be made according to recommended application scheme keeping following rules: 1. Firstly sensors, then actuators and in the end power line. For sensors is recommended twisted pair line (MK 2x0.75/TP 03/41/MTP 226/70), keeping distance from power wires (min.30 cm) and shield connect to PE wire. 2. Before screwing wires to terminal, put the sleeve endings to the end of the wires 3. Just before power supply connection check all input and output wires (sensors, actuating terms) for disconnection or short-circuit 4. Turn on the safety fuse and test function of actuators in manual mode 5. Check measured temperature values at collector, then in the loops and set initial system parameters. 4.4 PC connections Device offers possibility for connection to serial port of personal computer. This connection enable user to: ∗ comfortable set up all parameters of regulation ∗ not limited keeping records of gained energy ∗ watch regulation process from the living room „sofa“ and supervisor regulation From the hardware side of connection, there is a necessity for communication (physical layer converter for RS232 <=> 20 mA current loop) converter DX 5220, which is connected with two wires to connector field (P+, P–). Keep polarity during connection, right connection forces LED in DX5020 to light (pins of DX5020 should have about 2.7V), wrong connection (0,7V). A0650_1.odt 17 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. PW ER F E DX 4102 Fuse holder Serial PC port (RS232 or USB) SOLAR REGULATOR + DX5220 P+ P- S3 AG S4 AG L N P N X Y Power fuse L PE N Sensors: Actuators: Flow measuring: Note: D1 DG D2 S1 AG S2 AG P1 F Sk Sa Sh Sx PO Sk – collector temperature, Sa – exchanger temperature, Sx – return flow, Sh – auxiliary heating PO – power relay, that controls auxiliary heating (3 phase heating element), P1 – pump F -flow-meter connected to digital input installation bracket and fuse holder are under the top cover Fig.18 An example of regulator connections A0650_1.odt 18 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 2. DX 4102 1. 85.5 mm Open the regulator coverregulátora. by the tool Nástrojom otvoriť kryt 50.5 mm Podľa priloženej šablóny navrtať diery According to included scheme drill holes for dies. pre zápustky. Press dies to the prepared holes Do dier inštalovať zápustky. the zaskrutkovať. uppermost screw down. VrchnúInsert skrutku 3. Zavesiť nauppermost vrchnú skrutku. Hang upregulátor regulator on screw DX 4102 4. 5. Po pripojen í elektrickej inštalácie After wire connection check out function, a skontrolovaní funkcie nasunúť kryt push down the cover to the basis. regulátora na základňu. ZaskrutkovaťInsert dve spodné skrutky. the last two screws Fig.19 Device assembling A0650_1.odt 19 05/2007 Solar system regulator DX4102.G Duel Námestovo Ltd. 5. Technical data Power supply: 230V/50Hz Power rating: 230VA Output voltage: 230V/50Hz Output current limitation: 1A Fuse rating: 2 A, type T (slow reaction) Sensor temperature range: -25 ÷ +170 °C Sensors: DX 1083 (DUEL Námestovo, [1000 Ohm @ 25°C, 1670 Ohm @ 100°C)] Difference range: 0 ÷ 25 K Temperature accuracy: ± 1.5 K Time back up: 7 days Insulation protection: IP20 Operating ambient conditions. Ambient temperature: 5 ÷ 50 °C Air humidity: max 90% @ 30°C Air pressure: 70 ÷ 106 kPa Warranty: ● Manufacturer provides guarantee 36 month from the day of delivery ● Warranty refers only to the fault, which come into being by normal operation with sensor delivery. Do not refer to fault, which arises by inexpert service, incorrect storage, unsuitable environment and high power activity (spontaneous disaster, flood, fire, atmospheric discharge and so on.) ● User looses claim to warranty at devices, on those was execution hit ● Warranty also after-warranty service guards manufacturer A0650_1.odt 20 05/2007 Solar system regulator DX4102.G Notes: A0650_1.odt Duel Námestovo Ltd. 21 05/2007 Solar system regulator DX4102.G A0650_1.odt Duel Námestovo Ltd. 22 05/2007 Solar system regulator DX4102.G A0650_1.odt Duel Námestovo Ltd. 23 05/2007 Solar system regulator DX4102.G DUEL Námestovo s. r. o., Telefon / Fax: Email: Http: A0650_1.odt Duel Námestovo Ltd. Florinova 928 / 9, SK - 029 01 Námestovo +421 (0) 43 5591 092 / +421 (0) 43 5591 091 [email protected] www.duel-ltd.sk 24 05/2007