Operating and service manual 813 Mevap direction Alarm Description Not implemented yet 815 Mcond cur LO speed Description Cause Trouble shooting Condenser Motor Low Speed Current Fault Alarm Indication of defective motor or defective supply cables to motor Possible causes: • Condenser motor jammed or defective. • Condenser motor cable defective. • Bad connection in plug • Condenser motor cable wired wrongly in controller cabinet or motor. Accompanied alarms: • N/A. Trouble shooting: 1) Check the condenser motor fan can rotate freely. Turn off power first! Replace motor or make it turn freely again. 2) Check motor cable for damages. 3) Check that the condenser motor cable is mounted correctly. Criteria Condenser fan motor has exceeded current limit at low speed. 0.2 – 0.3 Amp Controller action None Consequence Test failed Elimination Alarm may then be deleted after test completed Log data Log Parm 1 X Parm 2 Active/Inactive INom Alarm X Alarm light Parm 3 Parm 4 Parm 5 I1 I2 I3 148 of 227 pages Slow flash