976
Internal sup HI
Warning
Description
Cause
Trouble
shooting
12 V supply voltage high on SMC6
Indication of controller internal voltage reference fault
Possible causes:
•
Defective 12 V power supply.
•
Defective main controller.
•
Short circuit between 24 V DC and 12 V DC
Accompanied alarms:
•
There may be other alarms, AL 971 and AL 973
•
AL 801 will be activated during FT- or PTI test.
Trouble shooting:
1) See trouble shooting for AL 974
Criteria
Controller
action
Internal power supply above 14 V DC
None
Log
X
Alarm
Alarm light
Off
Consequence
Less accurate readings from measurements and risk for damage to sensors
Elimination
Alarm will be marked as inactive in alarm list when supply voltage is correct. Alarm may
then be deleted
Log data
Parm 1
Parm 2
Active/Inactive Low limit
Parm 3
Parm 4
High limit
Actual value A/D channel
980
Tinternal LO
Description
Cause
Trouble
shooting
Controller Internal Voltage Reference Fault
Parm 5
Warning
Indication of controller internal voltage reference fault
Possible causes:
•
Defective power supply for main controller.
•
Defective main controller.
Accompanied alarms:
•
AL 801 will be activated during FT- or PTI test.
Trouble shooting:
1) Check if there are other active (sensor) alarms.
Clear these alarms first using their trouble shooting.
2) The main controller is defective.
Replace the main controller.
Criteria
Controller
action
Internal temperature sensor below -40°C (-40°F)
None
Log
X
Alarm
Alarm light
Parm 1
Parm 2
Parm 3
Parm 4
High limit
Actual value A/D channel
Off
Consequence
Elimination
Log data
Active/Inactive Low limit
Parm 5
The measured temperature is internal on the main controller and cannot be measured
180 of 227 pages