Download SERVICE MANUAL - Rogers Supply
Transcript
TTW SERVICE PROCEDURE IV Blower Testing and Replacement WARNING 115 volt potential exposure. Use caution when making voltage checks to avoid personal injury. Blower Testing Step 1. Position gas control power switch to “ON” position and adjust control to call for heat. Step 2. Remove the three screws (Phillips Screw driver) from control access cover on blower assembly and remove cover (see photo 7). Does blower energize Within 2 minutes? Y Connect manometer to pressure tap of blower. (see photo 8) Disconnect pressure switch tubing from blower. (see photo 8) N Pressure tap 8 7 Disconnect vent system from top of blower and remove vent adapter. (see photo 10) With blower running, and exhaust adapter removed from top of blower, is there a negative pressure of -2.15" to -2.30" W.C.? N N Determine voltage problem and correct. Y 10 9 Pressure switch tubing Does blower energize after 2 minutes, run for 30 seconds and shut down? Remove exhaust adapter See pressure switch testing Page 18 Is there 115vac across blue and green wires (see photo 13) 11 Y Y Blower OK Replace blower 12 N Disconnect cord set shown in photo 9. Is there 115VAC across terminals shown in photo 11 Y Incorrect supply voltage polarity N Determine power source problem and correct. Y Check power cord for damage. N Replace blower Page 20 Y N N Is there 115 VAC at wall outlet? Is there 115VAC across terminals shown in photo 12 ? Y Repair or replace power cord Replace cord set Reconnect cord set shown in photo 9, is there 115VAC between blue wire and green ground wire (see photo 13) N Does cord set N have electrical continuity? Y Replace blower Green ground wire Y 13 Blue wire Replace gas control Shown with pressure switch removed. Page 20