Download AIR CONDITIONER
Transcript
FILE NO. SVM-09030 9-5-5. Only outdoor fan does not operate Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? NO See "Power can not be turned on". YES Does the power turn on by pushing the [ ] button of the remote control? NO See "Power can not be turned on". YES Is the voltage across the indoor terminal ( 2 - 4 : Heat pump model, 1 - 2 : Cooling only model) AC 220-240V? NO Relays (RY03) or Q09 or IC30 is failure. NO Correct cabling between indoor and outdoor units. NO Cables between indoor and outdoor units are defective. NO Correct the wire or replace the defective cords. YES Is cable connection between indoor and outdoor units correct? YES Is the voltage across the terminal ( 2 - 4 : Heat pump model, 1 - 2 : Cooling only model) AC 220-240V? YES Are all the cords for outdoor fan motor normal? YES Is the outdoor fan motor winding normal? (Check the winding resistance) NO Outdoor fan motor is defective. YES Is the capacitor for compressor normal? YES NO Capacitor for outdoor fan motor is defective. Outdoor fan motor is defective. – 50 − Replace the P.C. board.