OPERATION WOOD AND CARBON
1.1
DESCRIPTION
1.1.2
1.1.1
INTRUDUCTION
The boilers are supplied in three separate
parcels:
– Boiler body assembled and equipped with
loading port, ash boxes port, smoke chamber with blast gate damper, ash collection
basin and thermostatic draught regulator.
Bag containing: 2 handles for the ports, a
screw with bakelite knob for the manual
The cast iron “SOLIDA PL” boilers are a valid
solution for the present energetic problems,
since they can run with solid fuels: wood
and carbon.
“SOLIDA PL” boilers conform to Directive
PED 97/23/CEE.
1.1.3
SUPPLY
adjustment of the blast gate damper, a contact spring for the bulb of the thermometer
and the M6 lever to be fixed at the blast gate
damper. “Test certificate” to be kept with
the documents of the boiler. Miscellaneous
accessories required to use the boiler with
pellets (see Section 2 in the manual).
– Cardboard box for casing with thermometer and documents bag.
DIMENSIONS
308
470
197
L
88
=
=
M
1020
845
1080
307
Ø147
FIXTURES
M C.H. flow 2”
(UNI-ISO 7/1)
R C.H. return 2”
(UNI-ISO 7/1)
S Boiler drain 1/2”
(UNI-ISO 7/1)
P
L
P
1.1.4
SOLIDA 5 PL
555 mm
390 mm
SOLIDA 8 PL +
855 mm
690 mm
220
S
185
R
160
Fig. 1
TECHNICAL FEATURES
Model
SOLIDA 5 PL
SOLIDA 8 PL +
25.6 (22,000)
39.5 (34,000)
2
2
≥4
≥2
≥4
≥2
dm3
34.0
59.5
mbar
0.12
0.18
kW (kcal/h)
Carbon heat rate *
Performance class
Duration of a coal load
h
Duration of a wood load
h
Load volume
Minimum chimney depression
Number of elements
n°
5
8
Max. operating temperature
°C
95
95
Min. temperature of water returned to the plant
°C
50
50
Max working pressure
bar
4
4
Test pressure
bar
6
6
Boiler capacity
l
31
43
kg
245
350
Weight
* The heat rate will be reduced with about 10% for the operation with hard wood (birch – oak – olive).
1.1.5
HEAD LOSSES
400
SOLIDA 8 PL +
7
p mm H2O
300
6
SOLIDA 5 PL
200
100
0
40
3
0
1
4
2
3
4
3/h
3
Flow
rate m
h)
PORTATA
(m
Fig. 2