RWF 50/55 - Microprocessor regulator - Setting parameters PArA
Parameter
Display Value range
Factory
setting
Set 50.2/55.2
Ecoflam
(passive probe)
FT-TP/1000
Set 50.2/55.2
Ecoflam
(active probe)
QBE...- P...
10
8
0,1
Proportional band
¹
Pb1
Derivative time
dt
0...9999 s
80
60
50
rt
0...9999 s
350
180
180
1
1
15
15
15
-5
-5
-0,5
3
3
3
5
5
1
0
0
0
Integral action time
Dead band (neutral
zone) ¹
b
db
Controlling element
running time
tt
1...9999 digit
0,0...999,9 digit
10...3000 s
Switch-on threshold
Heating controller ¹
HYS1 1999...0,0 digit
Switch-off threshold
stage II
Heating controller ¹
HYS2
Switch-off threshold
Heating controller ¹
0,0... HYS3 digit
HYS3 0,0...9999 digit
q
Response threshold
0,0...999,9
0,5
Set 55.2 Ecoflam (external probe)
Outside temperature
Curve point1 ¹
At 1
-40......120
- 10
-10
-10
Boiler temperature
Curve point 1 ¹
Ht 1
SPL......SPH
60
68
68
Outside temperature
Curve point 2 ¹
At 2
-40......120
20
22
22
Boiler temperature
Curve point 2 ¹
Ht 2
SPL......SPH
50
48
48
¹ Setting of decimal place has an impact on this parameter.
)
Note! When using the RWF50… as a modulating controller only, or as a modulating controller without the burner
release function (1P, 1N), parameter HYS1 must be set to 0 and parameters HYS2 and HYS3 must be set to their maximum values.
Otherwise, for example, when using default parameter HYS1 (factory setting -5), the 3- position controller is only released
when the control deviation reaches -5 K.