Installation
SN2008/IR
Rough-In Dimensions for Supplies and Drain
Notes
(mm)
Key
Maximum flow rate required to washfountain is 1.5 GPM. Size supply
lines accordingly.
Supplies from Below: Stub up 2-1/2" (64).
Supplies from Above: Supplies must be located on centers of
dimensions shown to pass through washfountain shroud and
sprayhead.
1/2" Supply: Nominal Copper Tube
1-1/2" NPT Drain Stub up 3" (76) from Floor
Conduit Location (Recommended)
Drain through floor: Stub up 3" (76).
Supplies from Below or Through Wall
Supplies from Above
Type B
Centrally rising vent (P-Trap
furnished with unit.) Use for units
with paper towel Dispensers
and/or shrouds.
Type A
Off-line vent (P-Trap
supplied by Installer.)
Type H
Centrally rising vent (P-Trap
furnished with unit.) Use for units
with paper towel Dispensers
and/or shrouds.
Type O
Off-line vent (P-Trap
supplied by Installer.)
Top View
Top View
4-1/2" 4-1/2"
(114) (114)
H
C
Type H
3-1/4" (83)
4" (102)
Type B
27/32" (21) H
4" (102)
5"
(127)
27/32" (21)
Type A
C
1-3/16"
(30)
5"
(127)
Type O
Remote mounting of transformers with 24VAC
electrical supply to washfountain is recommended.
UPC and IPC restrict the vertical distance from the fixture outlet to the trap
weir to not more than 24" (610). Check state and local codes for variances.