Download 2. General
Transcript
9. Malfunctions and remedial measure faults Faults Causes Elimination Battery voltage too high - Battery not available - Battery contact error - Insert a battery - Check battery polarity and seat Relay error - Relay contact in control unit is stuck together - The plant is currentless - The display is defective - Replace the control unit The display of the control does not show anything or shows the message "Mains failure" - Check pre-fuse and / or earth leakage circuit breaker - Call after-sales service, adapt maximum extraction time - Maximum extraction time too short - Uncontrolled inflow to the plant (e.g. rain water, plant leaks) - Water cannot drain off (e.g. backup, compressed air syphon hose not in drain) - Floating switch too low (setting see floating switch) - Ensure that there is no inflow of external water into the plant - Provide free drainage. - Replace the floating switch - Control the impact load - If it is not possible to restore the function even during longer manual operation, remove the compressed air syphon and rinse clean - Adapt the inflow quantities or expand the plant The water level in the preliminary sedimentation is exceptionally high, while the aeration exhibits a normal water level - Excessive impact load on plant - Compressed air syphon for the feeding is clogged - Connect the plant to the grid - External water may not penetrate into sewage treatment plants for a longer period of time. If necessary seal concrete tank or eliminate other causes. The water level in the preliminary sedimentation and in the aeration is exceptionally high - Plant undersized - Mains failure - Exceedingly high external water inflow. In case of heavy rainfalls due to surface water or on soaked soils due to a leaky tank. - Compressor does not work - Compressed air syphon for clear water extraction is clogged - Pressure hose leaky or no longer connected. - Check function in manual mode. If it is not possible to start up the compressor, call the after-sales service. - If it is not possible to restore the function even during longer manual operation, remove the compressed air syphon and rinse clean. - Check connections and pressure hose and if necessary restore The display shows the message "Extraction" Other possible faults 126