Transcript
104 4. Functions and options Outdoor temperature sensor: Arrangement/Heat. circuit/hc/Expert/Sen. outdoor adjustment range: 1 ... 10 factory setting: sensor 7 Adjustment channel for allocating the outdoor temperature sensor. The default is sensor 7 – this can be reallocated if needed. A sensor which is already in use can be allocated without influencing its original function in the system. Note: If additional external modules HKM are used, only 1 outdoor temperature sensor is required. In order to ensure that all heating circuits use the same outdoor temperature, adjust to sensor 13. Afterheating Arrangement/Heat. circuit/hc/Expert/aft.-heat selection: „None“, „Therm.“, „Store“ factory setting: „None“ Arrangement/Heat. circuit/hc/Expert/DT ah on adjustment range: -15,0 ... 49,5 K factory setting: 2,0 K Arrangement/Heat. circuit/hc/Expert/DT ah off adjustment range: -14,5 ... 50,0 K factory setting: 8,0 K The set flow temperature is compared with the temperature at one or two store (buffer) reference sensors (differential control). If this temperature differential is to small (DTHon), afterheating will be activated. It will be switched off, if the differential (DTHoff) between store and set flow temperature is large enough. Select the after-heating type via the parameter “Aft.Heat.“ (“None“, “Therm.“, or “Store“). If “None“ is selected, no afterheating will be carried out. If “Therm.“ is selected, the set flow temperature is compared with a store reference sensor. If “Store“ is selected, the comparison is made with 2 reference sensors. The switching conditions to both reference sensors have to be fulfilled. Sensor 1 store Arrangement/Heat. circuit/hc/Expert/S1 Store adjustment range: 1 ... 10 factory setting: 4 With this parameter, the 1st reference sensor for heating circuit afterheating can be selected. Sensor 2 store Arrangement/Heat. circuit/hc/Expert/S2 store adjustment range: 1 ... 10 factory setting: 5 With this parameter, the 2nd reference sensor can be selected for store-dependent afterheating.