Download DANGER WARNING CAUTION
Transcript
English Packaging Description The ConneXium TeSysPort TCSEQM113M13M package contains: • TCSEQM113M13M TeSysPort • Quick Reference Guide (this book) Introduction Summary The ConneXium TeSysPort adds Ethernet connectivity to Telemecanique's TeSys product line. It is the interface device between a single TeSys Modbus/RTU (RS-485) device and the physical layer of Modbus/TCP networks in slave mode. TeSysPort requires a separate power supply. An Ethernet device connected to the TeSysPort is the client/master. A Modbus device, such as TeSys U or TeSys T, connected to the TeSysPort is the server/slave. Any requests from an Ethernet device are sent to the TeSys U and TeSys T devices transparently. About TeSys Motor Management System TeSys Motor Management System includes 2 different solutions: • The TeSys T Motor Management System is an intelligent motor protection relay (IMPR) that provides current-related protections, and has 6 inputs and 4 outputs, as well as an extension module, which extends the functionality of the IMPR by adding voltage-related protection and 4 additional inputs. The TeSys T Motor Management System offers protection, control, and monitoring capabilities for single-phase and 3-phase induction motors. The current range covered is 0.4 to 100 A with internal current transformer and 100 to 810 A with external current transformer. • TeSys U Motor Starter is a modular, intelligent motor starter that provides power control and current-related protections. Up to 15 kW circuit breaker and contactor are integrated inside the TeSys U starter controller. Above 15 Kw to 450 kW circuit breaker and contactor are external to the TeSys U controller. About Modbus The Modbus protocol is a master/slave protocol that allows one master to request responses from slaves or to take action based on their requests. The master can address individual slaves or can initiate a broadcast message to all slaves. Slaves return a message (response) to queries that are addressed to them individually. Responses are not returned to broadcast queries from the master. About Modbus/TCP Communications TeSysPort supports up to 6 simultaneous Modbus/TCP connections. Attempting to use more than 6 connections results in a degradation of performance because TeSysPort closes the connection with the longest idle time to accept a new connection request. Note: If your system uses an NOE module, use NOE firmware version 3.5 or higher. If your system uses an ETY module, use ETY firmware version 3.1 or higher. If your system uses a Unity-compatible CPU with an integrated Ethernet port, use CPU firmware version 2.0 or higher. If Powersuite is used for configuration over Ethernet, the minimum revision should be version 2.4. 2 31007460 4/2007