Packaging Description
The ConneXium TeSysPort TCSEQM113M13M package contains:
• TCSEQM113M13M TeSysPort
• Quick Reference Guide (this book)
Introduction
Summary
The ConneXium TeSysPort adds Ethernet connectivity to Telemecanique's TeSys
product line. It is the interface device between a single TeSys Modbus/RTU (RS-485)
device and the physical layer of Modbus/TCP networks in slave mode. TeSysPort
requires a separate power supply. An Ethernet device connected to the TeSysPort is
the client/master. A Modbus device, such as TeSys U or TeSys T, connected to the
TeSysPort is the server/slave. Any requests from an Ethernet device are sent to the
TeSys U and TeSys T devices transparently.
About TeSys Motor Management System
TeSys Motor Management System includes 2 different solutions:
• The TeSys T Motor Management System is an intelligent motor protection relay (IMPR) that
provides current-related protections, and has 6 inputs and 4 outputs, as well as an extension
module, which extends the functionality of the IMPR by adding voltage-related protection and
4 additional inputs. The TeSys T Motor Management System offers protection, control, and
monitoring capabilities for single-phase and 3-phase induction motors. The current range
covered is 0.4 to 100 A with internal current transformer and 100 to 810 A with external
current transformer.
• TeSys U Motor Starter is a modular, intelligent motor starter that provides power control and
current-related protections. Up to 15 kW circuit breaker and contactor are integrated inside
the TeSys U starter controller. Above 15 Kw to 450 kW circuit breaker and contactor are
external to the TeSys U controller.
About Modbus
The Modbus protocol is a master/slave protocol that allows one master to request
responses from slaves or to take action based on their requests. The master can
address individual slaves or can initiate a broadcast message to all slaves. Slaves
return a message (response) to queries that are addressed to them individually.
Responses are not returned to broadcast queries from the master.
About Modbus/TCP Communications
TeSysPort supports up to 6 simultaneous Modbus/TCP connections. Attempting to
use more than 6 connections results in a degradation of performance because
TeSysPort closes the connection with the longest idle time to accept a new connection
request.
Note:
If your system uses an NOE module, use NOE firmware version 3.5 or higher.
If your system uses an ETY module, use ETY firmware version 3.1 or higher.
If your system uses a Unity-compatible CPU with an integrated Ethernet port, use CPU firmware
version 2.0 or higher.