11.98 Technical data Power reduction at increased coolant temperature om 14.1 The rated current must be reduced according to Figure 14.2 for cooling medium temperatures exceeding 40°C. Cooling medium temperatures > 50°C are not permissible. .c permissible rated current in % 100 ua ls 90 80 75 60 Coolant temperature in °C 10 30 40 50 Maximum permitted rated current depending on coolant temperature ar tM Figure 14.2 20 an 70 14.2 Power reduction at altitudes > 1000m above MSL lP The rated current must be reduced as shown in Figure 14.3 in the event of installation altitudes > 1000 m above mean sea level. Installation altitudes > 2000 m above MSL (please enquire) ca permissible rated current in % lec tri 100 90 80 70 .E 60 0 2000 3000 4000 100 90 80 70 60 0 1000 Installation altitude in m above sea level 2000 3000 4000 Installation altitude in m above sea level Maximum values for rated current and rated voltage depending on installation altitude ww w Figure 14.3 1000 permissible rated current in % Siemens AG 6SE7087-6AC85-0AA0 Common Rectifier Operating instructions ENGLISH 14-3