4.2.1 Relay output Control terminal X10 Ter. Description 1 ... 3 Relay output, floating change-over contact, response time approx. 40 ms, maximum contact load: − make contact: AC 5 A / 240 V, DC 5 A (ohmic) / 24 V − break-contact: AC 3 A / 240 V, DC 1 A (ohmic) / 24 V 4.2.2 GB External 24 V power supply The bidirectional control terminals X210A.1/ X210A.2 can be used as a voltage output or voltage input. By connecting an external power supply of DC 24 V ±10% to terminals X210A.1/X210A.2, the function of inputs and outputs as well as the communication can be parameterized and maintained, even when mains voltage is off. Input voltage range Rated input current Peak inrush current External fuse Safety Requirements to be met by external power supply DC 24 V ±10% Max. 1.1 A Typeically: < 25 A Via standard fuse elements for rated current, characteristic: slow Safety extra low voltage (SELV) according to EN 61800-5-1 CAUTION The digital inputs and the DC 24 V terminal of the electronic control equipment can withstand external voltage up to DC 30 V. Avoid higher voltage levels. Higher voltages may destroy the unit. 4.3 Auxiliary voltage terminals ACU size 8 (160...400 kW) When using an ACU501 or ACU601 device the connection of 3 x AC 400 V on terminal X13 is necessary. 1…6 7 8 9 10 Terminal X13 Not used PE L1 L2 L3 Connection Connection power ≥ 1,2 kW Connection voltage 400 V +- 10 % Connection fre50 / 60 Hz quency 62 Quick Start Guide ACU 02/15