Download TopControl Positioner Type 8630
Transcript
Cutoff Close tight function Factory setting: CUT = 1 %; CUT = 99% The closed tight function ensures that the valve is tightly closed outside the control range. Specification of a value (%) from which the actuator air is completely exhausted or supplied with air. The opening or resumption of the control operation takes place with a hysteresis of 1% (refer to Fig. 6.9). Exhaust aired (0 % inactive) Range: 0.0 ... 10.0 % for complete exhausting Filled with air (100 % inactive) 90.0 ... 100 % for complete air supply Plug travel [%] Programmable from 75,0 to 100,0 % Setpoint [%] Fig. 6.9: Closed tight function Programmable from 0,0 to 25,0 % Dir.cmd Direction of command of the setpoint of the actuator Factory setting: DIR.CRISE With this additional function, the direction of action according to setpoint of the actuator and the input signal (Fig. 6.10). Rise direction (i.e. 4 mA bzw. 0 V → 0% 20 mA bzw. 5/10 V → 100%) Fall direction (i.e. 4 mA bzw. 0 V → 100% 20 mA bzw. 5/10 V → 0%) 104 Operating instructions no. 800607