TECHNICAL DATA 9.1.6 Communication options Slot for optional interfaces 1x slot for interface cards Communication interfaces Signal inputs Relay output contactors Optional interface cards: SNMP adapter basic (article number: DW7SNMP30) SNMP adapter professional (article number: DW5SNMP30) Relay module (article number: PHXNOV-I) AS400 interface (article number: PHXAS400I) RS-232 (DB-9) USB 2 x programmable signal inputs for the display of building alarm or other use 1 x 3-pole connection with one 1 selector switch Table 20: Communication options 9.1.7 Environment and safety Overvoltage protection EMC Certificate EMC (emissions) Safety Approval Protection type Operating temperature Storage temperature Transport temperature Relative air humidity Operating height Transport height Audible noise Creepage current EN 61000-2-2 EN 61000-4-2, Level 3 EN 61000-4-3, Level 2 EN 61000-4-4, Level 2 (also for signal interfaces) EN 61000-4-5, Level 3 Criteria A EN 61000-4-6, Level 2 EN 61000-4-8, Level 2 EN 61000-4-11 CE according to IEC/EN 62040-2, Emissions: Category C1, Immunity: Category C2 IEC 62040-2:ed2:2005 / EN 62040-2:2006 EN 62040-1:2008, EN 60950-1 CE IP20 0°C to 40°C in online mode, NOTE: The overheating protection switches the load to bypass mode in the event of overheating. -20°C to 40°C with batteries -15°C to 60°C without batteries -25°C to 55°C 5 - 90% noncondensing Up to 3000 meters above sea level Up to 10,000 m above sea level <50dBA at 1 m typical <1.5mA Table 21: Environment and safety specifications 143 / 222 XS700-XS3000_manual_ger_eng_it_V1.1.2.doc ........................................................... R. Kistler