Download Benutzerhandbuch
Transcript
OPERATION Each UPS system has two configurable load segments: Load segment 1: The upper or left power outlet Load segment 2: The lower or right power outlet (see "Rear sides of the UPS systems" under Technical Data). To control the load segments via the display: 1. Press any button to activate the menu options. Select "CONTROL" and "LOAD SEGMENTS". 2. Set the desired load segment using the or buttons to "ON" or "OFF" and select the button to confirm the selection. 3. Set the other load segment, if required. To set the waiting time for restart and shutdown of the individual load segments: 1. Press on any button to activate the menu options. Select "SETTINGS", "USER SETTINGS" and then "AUTOMATIC START DELAY". 2. Set the waiting time for the restart of a load segment and confirm this setting using the button. 3. Set the other load segment, if required. 4. Select "AUTOMATIC ON BATTERY SHUTDOWN". 5. Set the waiting time for the shutdown of a load segment and confirm this setting using the button. 6. Set the other load segment, if required. 109 / 222 XS700-XS3000_manual_ger_eng_it_V1.1.2.doc ........................................................... R. Kistler