Download AirSmart-Controller - Schneider
Transcript
5. Error Management Shutdown faults Shutdown Shutdown text Description Action # 110 HIGH SEP PRES Pressure in separator tank > (Preset Value) Check for sources of high system pressure # 111 SHORTED XDUCER XD4 Connection to pressure transducer XD4 is shorted Check wiring between pressure transducer XD4 and controller # 112 OPEN XDUCER XD3 Connection to pressure transducer XD3 is open Check wiring between pressure transducer XD3 and controller # 113 HIGH RESVR PRES Pressure at airend discharge > (Preset Value) Check for sources of high system pressure # 114 SHORTED XDUCER XD3 Connection to pressure transducer XD3 is shorted Check wiring between pressure transducer XD3 and controller # 115 OPEN XDUCER XD2 Connection to pressure transducer XD2 is open Check wiring between pressure transducer XD2 and controller # 116 HIGH INT PRES Pressure in interstage pipe > (Preset Value) Check for sources of high system pressure # 117 SHORTED XDUCER XD2 Connection to pressure transducer XD2 is shorted Check wiring between pressure transducer XD2 and controller # 118 OPEN XDUCER XD1 Connection to pressure transducer XD1 is open Check wiring between pressure transducer XD1 and controller # 120 SHORTED XDUCER XD1 Connection to pressure transducer XD1 is shorted Check wiring between pressure transducer XD1 and controller # 121 OPEN THERM T5 Connection to thermistor T5 is open Check wiring between thermistor T5 and controller # 122 HIGH PKG DISCH TMP Temperature at package discharge > (Preset Value) Check air cooler functionality or reduce package power # 123 SHORTED THERM T5 Connection to thermistor T5 is shorted Check wiring between thermistor T5 and controller # 124 OPEN THERM T4 Connection to thermistor T4 is open Check wiring between thermistor T4 and controller # 125 HIGH SEP TEMP Temperature in separator > (Preset Value) Check oil cooler system functionality or reduce package power 37