Download Installation and Operating Instructions
Transcript
Troubleshooting 5.6 Troubleshooting Coaxial Cable If there is water or other conductive material in the conduit (ie.: Excessive wire lube) it can change the electrical properties of the coax cable and cause the system to perform poorly. Moisture in the conduit may not be detected by the following test. The only sure way is to inspect the coax and associated conduit for trapped water. 1. Disconnect all three wires of the coaxial cable at the electronic unit. 2. Disconnect all wires at the sensing element end of the coax. 3. Using an ohmmeter, measure between two of the coaxial cable conductors. Note any reading. Repeat for all three conductors. All readings should show an open circuit, (infinite resistance). 4. Check for continuity of each conductor. Short out two of the coaxial cable conductors and measure these two conductors at the other end. A reading < 10ohms indicates a good cable. Move the short to the third conductor and repeat. 63