7-2
Communicating with PanelView and RSView Products
The Logix5000 controller in the local chassis can be any of the
following, with their ControlNet communication modules:
• 1756 ControlLogix controller with a 1756-CNB or 1756-CNBR
communication module in the chassis
• 1769-L32C or 1769-L35CR CompactLogix controller
• 1789 SoftLogix controller with a 1784-PCIC, 1784-PCICS or
1784-PKTCS communication card
• 1794 FlexLogix controller with a 1788-CNx ControlNet communication
card
• PowerFlex 700S with DriveLogix controller and a 1788-CNx
ControlNet communication card
Make sure that:
• the ControlNet communication modules are connected to a
scheduled ControlNet network
• all wiring and cabling is properly connected
Determining Connections to
PanelView Terminals
How you establish communication between a PanelView or
PanelView Plus terminal and a Logix5000 controller over ControlNet
depends on how you want to use controller connections.
Terminal type:
Type of communications:
PanelView Standard: PanelView Plus:
scheduled (always connected)
supported
supported in
version 3.2 and greater
unscheduled connected
not supported
supported
unscheduled unconnected
supported
not supported
A Logix controller supports up to 40 outgoing and 3 incoming unconnected
buffers. This limited number of incoming unconnected buffers limits how
many PanelView Standard terminals can request data from a controller.
Publication CNET-UM001B-EN-P - May 2005