ENG 9. TECHNICAL SPECIFICATIONS AND PRODUCT CODES 9.1 Technical specifications Power supply Power supply Model Voltage IR33x(V,W,Z,A,B,E)7Hx(B,R)20 DN33x(V,W,Z, A,B,E)7Hx(B,R)20 IR33x(V,W,Z,A,B,E)7LR20, DN33x(V,W,Z,A,B,E)7LR20 115 to 230 Vac(-15%...+10%), 50/60 Hz 6 VA, 50 mA~ max IR33x(V,W,Z,A,B,E)9Hx(B,R)20 DN33x(V,W,Z, A,B,E)9Hx(B,R)20 IR33x(V,W,Z,A,B,E)9MR20, DN33x(V,W,Z,A,B,E)9MR20 Insulation guaranteed IR33x(V,W,Z,A,B,E)x(7, 9)Hx(B,R)20 by the power supply DN33x(V,W,Z,A,B,E)x(7, 9)Hx(B,R)20 12 to 24 Vac (-10%...+10%), 50/60 Hz 4 VA, 300 mA~ max 12 to 30 Vdc 300 mA - max Only use SELV power supply, maximum power 100 VA with 315 mA fuse on the secondary 115 to 230 Vac(-15%...+10%), 50/60 Hz 9 VA, 90 mA~ max 24 Vac (-10%...+10%), 50/60 Hz 24 Vdc (-10%...+10%) Only use SELV power supply insulation from very low voltage parts insulation from relay outputs IR33x(V,W,Z,A,B,E)x(7, 9)x(L, M)R20 DN33x(V,W,Z,A,B,E) x(7, 9)x(L, M)R20 insulation from very low voltage parts insulation from relay outputs Inputs B1 (PROBE1),B2 (PROBE2) Power 12 VA, 450 mA~ max 450 mA - max reinforced 6 mm in air, 8 mm on surface 3750 V insulation main 3 mm in air, 4 mm on surface 1250 V insulation to be guaranteed externally by safety transformer reinforced 6 mm in air, 8 mm on surface 3750V insulation NTC, NTC-HT, PTC, PT1000 NTC, NTC-HT, PTC, PT1000, PT100, TcJ, TcK, 0-5 V rat, 0-1 Vdc, 0-10 Vdc, -0.5-1,3 Vdc, 0-20 mA, 4-20 mA Type of probe Type of probe Probe power supply Relay outputs DI1, DI2 voltage-free contact, contact resistance < 10 Ω, closing current 6 mA Maximum distance of probes and digital inputs less than 10 m Note: in the installation, keep the power and load connections separate from the probe, digital inputs, repeater display and supervisor cables. NTC std. CAREL 10 kΩ at 25 °C, range –50T90 °C measurement error: 1 °C in the range –50T50 °C 3 °C in the range +50T90 °C NTC-HT 50 kΩ at 25°C, range –40T150 °C measurement error: 1,5 °C in the range –20T115 °C 4 °C in range outside of -20T115 °C PTC 985 Ω at 25 °C, range -50T150 °C measurement error 2 °C in the range –50T50 °C 4 °C in the range +50T150 °C PT1000 1097 Ω at 25 °C, range -50T150 °C measurement error: 3 °C in the range –50T0 °C 5 °C in the range 0T150 °C NTC std. CAREL 10 kΩ at 25 °C, range –50T110 °C measurement error: 1 °C in the range -50T110 °C NTC-HT 50 kΩ at 25°C, range –10T150 °C measurement error: 1 °C in the range -10T150 °C PTC 985 Ω at 25 °C, range -50T150 °C measurement error 1 °C in the range -50T150 °C PT1000 1097 Ω at 25 °C measurement error: 1 °C in the range –50T200 °C 2 °C in the range -199T800 °C PT100 109,7 Ω at 25 °C measurement error: 1 °C in the range –50T200 °C 2 °C in the range -199T800 °C TcJ isolated 52 μV/ °C measurement error: 2 °C in the range –50T200 °C 4 °C in the range -100T800 °C TcK isolated 41 μV/ °C measurement error: 2 °C in the range –50T200 °C 4 °C in the range -100T800 °C 0-5 V rat Impedance measurement of 50 kΩ 0.3 % Full scale 0-1 Vdc Impedance measurement of 50 kΩ 0.3 % Full scale 0-10 Vdc Impedance measurement of 50 kΩ 0.3 % Full scale -0.5-1,3 Vdc Impedance measurement of 50 kΩ 0.3 % Full scale 0-20 mA Impedance measurement of 50 Ω 0.3 % Full scale 4-20 mA Impedance measurement of 50 Ω 0.3 % Full scale 12 Vdc (rated), maximum current supplied 60 mA ; 5 Vdc (rated), maximum current supplied 20 mA EN60730-1 UL 873 models relay 250 V~ oper. 250 V~ oper. cycles cycles IR33x(V,W,Z,B,E)x(7, 9)x(L, M)R20 D01, D02 8(4) A su N.O. 100000 8A res 2FLA 12LRA C300 30000 DN33x(V,W,Z,B,E)x(7, 9)x(L, M)R20 D03, D04 6(4) A su N.C. IR33x(V,W,Z,B,E)x(7, 9)Hx(R,B)20 (**) 2(2) A su N.O. e N.C. DN33x(V,W,Z,B,E)x(7, 9)Hx(R,B)20 ir33 universale +030220801 - rel. 2.0 - 16.04.2010 54