Set up Mode on the signal conditioning instrument Level Signal current Sensor Mode A Overfill protection Signal lamp - sensor Signal lamp - signal conditioning instrument approx. 8 mA Green Mode A Overfill protection approx. 16 mA red Mode B Dry run protection approx. 16 mA Mode B Dry run protection approx. 8 mA red Green Fault signal (mode A/B) any <2.3 mA 30061-EN-060830 flashes red OPTISWITCH 3000 C - with two-wire output 19