Download 1 - Beijer Electronics
Transcript
FX3U Series Programmable Controllers 10 Input Wiring Procedures (Input Interruption and Pulse Catch) User’s Manual - Hardware Edition 1 Pulse Catch (M8170 to M8177) The PLC (main unit) is provided with a pulse catch function and has 8 pulse catch input points. → For details on programming, refer to the programming manual. 10.5.1 Allocation of special memories to Iinput numbers (ON duration of input signals) M8170 X001 M8171 X002 M8172 X003 M8173 X004 M8174 X005 M8175 X006 M8176 X007 M8177 ON duration of input signal 3 5µs or more Product Introduction Contact on sequence program X000 2 Features and Part Names Input No. Introduction 10.5 10.5 Pulse Catch (M8170 to M8177) 50µs or more 4 Specifications 10.5.2 Cautions for pulse catch 1. Non-overlap of input numbers Example: When the pulse catch input contact M8170 is used, X000 is occupied. Therefore, it is impossible to use C235, C241, C244, C246, C247, C249, C252 and C254, input interruption (including delay interruption) pointers I000 and I001 and SPD, ZRN, DSZR and DVIT instructions at the same time. • The wiring length should be 5 m (16’4") or less. • Connect a bleeder resistance of 1.5kΩ (1 W or more) to the input terminal, so that the sum of the load current of the open collector transistor output on the other side device and the input current of the main body is 20 mA or more. 6 System Configuration 2. Cautions in wiring 5 Version and Peripheral Devices The input terminals X000 to X007 can be used for high-speed counter, input interruption, pulse catch, speed detection (SPD) instructions and general-purpose input. Take care not to overlap the input numbers. 7 Input/Output Nos., Unit Nos. 8 Installation 9 Preparation and Power Supply Wiring 10 Input Wiring 179