Download User Manual
Transcript
EMA90 - USER MANUAL 11.10) ANALOG OUTPUT (OPTION) Selecting the analog output voice, the following programming page appears: • Out Index, expresses the number of output to select or program, which are present on the hardware of the instrument. • Type, allows to select the value of current output, (disabled, 0-20mA, 420mA). Through the up & down keys, it may be possible to select the type of the output current, by pressing the “ENTER” key the configuration is saved. • Measure Code, is the measure (see cap. 12) to associate at the analog output. • Min., full-scale value of the lower limit of the programmed value (Measure Code). Once the minimum full-scale has been programmed, the instrument automatically will associate the minimum current value (0 or 4 mA) at this value. • Max., full-scale value of the upper limit of the programmed value (Measure Code). Once the maximum full-scale has been programmed, the instrument automatically will associate the maximum current value (20 mA) at this value. If the minimum end-scale value is lower of maximum end-scale value, the out of current will be directly proportional at variable set, otherwise it will be inversely proportional. Minimum and maximum can be negative value. -51-