Step 2
Teaching
Teaching means to store the region and partial image as reference data for the measurement.
[Inspect] [Inspection] [Add item.] [Shape Search II] [Settings] Tab Page
1
2
Press [Teach].
3
4
5
Move the rectangle to the location to be measured.
6
Press [Back] to end teaching.
Place the object that is to be used as the measurement reference in front of the camera.
Drag the rectangle
to move it.
Drag a corner to
size the rectangle.
Press [OK].
Press [TEACH] on the lower right of the display.
The basic settings will be registered when teaching has
been completed.
The following data is stored as the measurement reference.
Item
Parameter
Description
Reference data
Model image
This is the partial image that is stored as the reference.
Reference position X
These are coordinates of the model image that are stored as reference.
Reference position Y
Step 3
Adjusting Judgement Parameters
[Inspect] [Inspection] [Add item.] [Shape Search] [Settings] Tab Page
1
2
Press [Judgement].
Press each parameter and set the range that is to be
judged as OK. Set the range for each of the following
parameters.
Continuous measurements will be performed for the images that are taken.
If more than one result was detected, you
can switch to a display for each result.
(Multi-point output must be enabled.)
Note
You can change the parameters for judgement conditions on the
Display Settings Display. Press [ ] [Display setting] on the right
of the display to switch to the Display Settings Display.
3
4
106
Press [OK] to accept the value.
Upper limit
Lower limit
Blue for OK. Red for NG.
Press [Back] to end making the setting.
Parameter
Setting
Description
Correlation
Range: 0 to 100
Defaults: Lower limit: 60, Upper limit: 100
Adjust the upper and lower limits of the correlation for an OK judgement.
Position X
Range: 99,999.9999 to 99,999.9999
Defaults: Lower limit: 99,999.9999,
Upper limit: 99,999.9999
Adjust the upper and lower limits of measurement position X for an
OK judgement.
Position Y
Range: 99,999.9999 to 99,999.9999
Defaults: Lower limit: 99,999.9999,
Upper limit: 99,999.9999
Adjust the upper and lower limits of measurement position Y for an
OK judgement.
Angle
Range: 180 to 180
Defaults: Lower limit: 180, Upper limit: 180
Adjust the upper and lower limits of angle for an OK judgement.
Count
Range: 0 to 32
Defaults: Lower limit: 0, Upper limit: 32
Adjust the upper and lower limits of the detection count for an OK
judgement.
Inspecting with the Shape Search II Inspection Item