G001-S
Soft
The internal temperature of the
grid module (G) is too high
•
•
G037-S
The output power of the module is •
reduced
7 Troubleshoot
Check the PowerRouter airflow (section 7.5.2)
Once the module cools down the error will
disappear and normal operation will resume
Contact your dealer if this error occurs frequently
EN
G002-S
Soft
An overvoltage occurred on the
•
power backbone. The grid module
(G) will be temporarily turned off
•
Once the voltage drops below the safe level the
error will disappear and normal operation will
resume
Contact your dealer if this error occurs frequently
G003-S
Soft
An undervoltage occurred on the •
power backbone. The grid module •
(G) will be temporarily turned off
(e.g. the load on the local out is
•
higher than the power available in
the PowerRouter)
Make sure the loads on the local out are turned off
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
G007-S
Soft
The voltage level on the local out •
is too high in a situation where no
voltage is expected
•
If this error occurs during installation make sure the
grid is connected to the “AC GRID” connection
When this error occurs during normal operation an
error has occurred in connection with the antiislanding safety requirements
Restart the system (section 7.5.1)
Contact your dealer if this error occurs frequently
•
•
G011-S
Soft
An undervoltage occurred on the
local out. The local out will be
temporarily turned off.
•
•
G012-S
Soft
An overvoltage occurred on the
local out. The local out will be
temporarily turned off (e.g. a very
high load connected to the local
out was suddenly disconnected)
•
•
A short circuit was detected on
the PowerRouter local out
•
•
•
G013-H
Hard
•
•
G015-S
G023-H
Soft
Hard
Make sure the loads on the local out are turned off
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
Make sure the loads on the local out are turned off
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
Make sure the loads on the local out are turned off
Check the wiring connected to the local out for a
short
Restart the system (section 7.5.1)
There was an internal
communication error within the
PowerRouter
•
•
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
The local out output was
overloaded
•
•
Turn off the loads connected to the PowerRouter
Restart the system (section 7.5.1)
•
•
Restart the system (section 7.5.1)
The system should recover from the error after the
restart
Contact your dealer if this error occurs frequently
G025-H
Hard
See P027-H
G028-H
Hard
An error occurred on one of the
internal voltage supplies of the
grid module (G)
G029-S
Soft
The grid module (G) start-up
procedure failed
G031-H
Hard
There was an overpower on the
output of the PowerRouter
G034-H
Hard
See P092-H
G036-H
Hard
See P098-H
•
•
•
After one minute the error will disappear and normal
operation will resume
Contact your dealer if this error occurs frequently
•
•
Turn off the loads connected to the PowerRouter
Restart the system (section 7.5.1)