Functions, Monitoring, and Protective Functions 9.2 Drive Functions 9.2.9.4 Maximum output frequency achieved by increasing the pulse frequency Maximum output frequencies achieved by increasing the pulse frequency By multiplying the basis pulse frequency (with integers), the following output frequencies can be achieved (taking into account the derating factors): Table 9- 4 1) 9.2.9.5 Maximum output frequency achieved by increasing the pulse frequency Pulse frequency [kHz] Maximum output frequency [Hz] 1,25 100 2 160 2,5 200 4 300 1) 5 300 1) The maximum output frequency is limited to 300 Hz due to the closed-loop control. Parameters • p0009 Device commissioning parameter filter • p0112 Sampling times pre-setting p0115 • p0113 Selects the minimum pulse frequency • p0115 Sampling times • p1800 Pulse frequency Drive converter cabinet units Operating Instructions, 10/2008, A5E00189855A 319