Setpoint channel and closed-loop control
7.2 Setpoint channel
Signal flow diagram
5)*WBUDPSXS
V
S
5)*7B6WDUW5GJ
V
S
5)*7B(QG5GJ
V
S
5)*WBUDPSGRZQ
V
S
I
6HWSBEHIRUHB5)*
U
QVHWSBDIWHUB5)*
U
S
Figure 7-3
S
S
S
W
Signal flow diagram: Ramp-function generator
Function diagram
FP 3060
Simple ramp-function generator
FP 3070
Extended ramp-function generator
• r1119
Ramp-function generator setpoint at the input
• p1120
Ramp-function generator ramp-up time
• p1121
Ramp-function generator ramp-down time
• p1130
Ramp-function generator initial rounding time
• p1131
Ramp-function generator final rounding time
• p1134
Ramp-function generator rounding type
• p1135
OFF3 ramp-down time
• p1136
OFF3 initial rounding time
• p1137
OFF3 final rounding time
• r1150
Ramp-function generator speed setpoint at the output
• p1151
Ramp-function generator configuration
Parameter
Note
The effective ramp-up time increases when you enter initial and final rounding times.
Effective ramp-up time = p1120 + (0.5 x p1130) + (0.5 x p1131)
Drive converter cabinet units
Operating Instructions, 10/2008, A5E00189855A