Download VLT Active Filter AAF005 Operating Instructions
Transcript
VLT Active Filter AAF005 4 How to Install 130BB520.10 For installation where the CT’s connection point can be moved below conections is also OK. For some few retrofit applications summation CT are needed to reassure that the capacitor current is not measured. PCC1 MF M 4 M Illustration 4.24: Capacitor bank mounted on PCC but CT’s installed to reassure that capacitor corrected current is not measured. Auto CT detection The VLT Active Filter is able to perform an auto detection of the installed CT. The ct auto detection can be conducted both while the system is running and at no load conditions. The filter injects a prefixed current of known amplitude and phase angle and is measuring the returned CT input. The performance is conducted on each phase individually and for several frequencies to reassure phase sequence and that harmonics of different correctly. The Auto CT detection is pending on the follow conditions: - Active filter bigger then 10% of CT RMS rate - CT’s installed on source (PCC) side (auto CT not possible for load side CT installation) - Only one CT per phase (not possible for summation CT’s) - CT’s are part of below standard range: Sec 1A Sec 5A 150 200 250 300 400 500 600 750 1000 1250 1500 2000 2500 3000 3500 4000 30 40 50 60 80 100 120 150 200 250 300 400 500 600 700 800 MG.90.V1.02 - VLT® is a registered Danfoss trademark 33