Setting up the System
3.3.4 Cable Connections to an AutroSafe Operating Panel
If the AS-2000 is to be connected to the Communication Module
BSL-310 inside an operating panel, the ribbon cable that is already
connected to the Communication Module BSL-310 must be
disconnected (see figure) before the other end of the cable from the
computer can be connected.
Note:
To avoid activating the internal buzzer when disconnecting the ribbon
cable from the Communication Module BSL-310, turn the power OFF
before disconnecting the ribbon cable. When you have connected the
external ribbon cable from the computer, turn the power ON.
Communication Module BSL-310
inside operating panel
To Power Supply
BSS-103A/02
Disconnect the ribbon cable to Connection
Module BSF-310B and connect the ribbon
cable from the serial port on computer.
All power connections to the Power Module BSS-310 are already
done. The Loop Driver Modules BSD-310 / BSD-311 are already
connected to the loops.
3.4 Starting AS-2000
 Start AS-2000 by double clicking at the shortcut you made in
chapter 3.2
 Select an available COM port on the PC.
User Guide, Loop Diagnostic Tool AS2000, Interactive Fire Detection Systems 116-P-ASAFE-AS/FGB Rev. H, 2012-06-15,