Download Excel CARE Control Icons User Guide
Transcript
CARE CONTROL ICONS High speed cooling factor Max. outside air temperature for opt.switch off Optimum for stop factor Factor adaption Parameter Number Descriptions ALPHABETIC REFERENCE P8 Units: Min/F Deg, Default: 10, Range: 0 to 100 Cool-down rate for optimum start. When the plant is turned on for cooling, this value is the number of minutes it takes to decrease room temperature by 1 degree This value can be automatically adjusted if the adaptation option is enabled. P9 Units: Deg, Default: 75, Range: 60 to 100 Maximum outside air temperature for optimum stop. When outside air temperature is at or above this value,the stop time will not be advanced in cooling mode. P10 Units: Min/F Deg, Default: 10, Range: 0 to 100 Optimum stop factor. For optimum stop during cooling, this value sets the amount of influence that the difference between room temperature and its setpoint has on advancing or retarding the optimum stop calculation. The base stop time is 120 minutes before the schedule stop time. For every degree that the room temperature is above setpoint, the base stop time will be decreased by the value of this parameter. For every degree that the room temperature is belowsetpoint, the base setpoint will be increased by the value of this parameter. Set to 0 to make optimum stop during cooling solely dependent on outside air temperature. Enable, disable, or new start/enable options. P3 P4 P5 P6 P7 P8 P9 P10 P11 Lowest preheat time for optimized preheat High-speed preheat factor (time required for X3 to rise 1K) Optimum stop OAT low limit for optimized shutdown (heating) Optimum stop factor (heating) Lowest cooling time for optimized cooling High-speed cooling factor (time required for X3 to decrease 1K) Maximum OAT for optimized shutdown (cooling) Optimum stop factor (cooling) Factor adaptation (for adapting P4 and P8): 0=enable 1=disable 2=new start/enable (restarts adaptive calculations, which overwrites previously gathered data and starts adapting P4 and P8 from scratch) P12 Room temperature setpoint (if X2 is not connected to a user address) EOV Operation EOV works exclusively on the basis of the “test room” method, that is, a room sensor is required. X3 is the input for the room sensor. In addition, EOV requires a room temperature setpoint (X2 or a parameter input), OAT sensor (X4), and the user address for the Time Program switch point (XD1). Optimized Start-up in the Heating Mode When the system is in heating mode (XD5=1), EOV displaces point switch-on (start-up) by time (tVHE) to guarantee room temperature setpoint is reached by start-up. The displacement of the switch-on point depends on the difference between the room temperature setpoint and actual room temperature. EOV assumes a linear room model. 133 74-5577–10 (US) EN2B-0184 GE51 R0404 (Europe)