Download Operating Instructions - Cont

Transcript
Startup
Startup with PC and MOVITOOLS® MotionStudio
I
5
0
5.10
Startup with PC and MOVITOOLS® MotionStudio
Start MOVITOOLS® MotionStudio in the Windows start menu:
Programs / SEW / MOVITOOLS MotionStudio 5.x/MotionStudio 5.x
Press the MOVITOOLS® MotionStudio [Scan] button to list all connected units in the unit
tree.
You can perform a startup by right-clicking on one of the units. You can find additional
information in the online Help.
5.11
Startup for MBG11A speed control module
You cannot simultaneously establish communication between MOVITRAC® B /
MBG11A and MOVITRAC® B / PC.
The MBG11A can simultaneously specify a setpoint for up to 31 MOVITRAC® B units.
5.11.1 Parameter settings
The following parameters must be set other than the factory setting in MOVITRAC® B.
When you use a FBG11B for setting the parameters, set the values indicated in
parenthesis:
•
P100: RS 485 (2)
•
P101: RS 485 (1)
•
P871: Set PA2 to "Speed [%]", then P876 PA data enable to "Yes".
The speed is now displayed:–100 % ... 100 % correspond to –nmax ... nmax.
5.11.2 Input terminals
The following input terminals must be connected with 24 V:
•
DI01 CW/Stop:positive + negative direction of rotation are possible by selecting the
+/- sign on the MBG11A.
•
DI03 Enable/Stop
Operating Instructions – MOVITRAC® B
59