F_28
Range
Direct Running on Power Up
【0】: Enable Direct running after power up
【1】: Disable Direct running after power up

When direct run on power up is selected by F_28 = 0 and the inverter is set to external run by
F_10 = 1, if the run switch is ON as power is applied, the inverter will auto start.
It is recommend that the power is turned off and the run switch is also off to avoid possibility of
injury to operators and damage to machines as the power is reapplied.
Note: If this mode is required all safety measures must be considered including warning
labels.
 When direct run on power up is disabled by F_28 = 1 and if the inverter is set to external run by
F_10 = 1, if the run switch is ON as power is applied, the inverter will not auto start and the
display will flash with STP1. It will be necessary to turn OFF the run switch and then ON again to
start normally.
F_29
Range
F_30




Software Version
---Fault Log Display (Latest 3 faults)
Range
---Last three faults are stored in a stack and whenever there is a new fault the previous faults
are pushed down the stack. So the fault stored in 2.xxx will be transferred to 3.xxx, and the
one in 1.xxx to 2.xxx. The recent fault will be stored in the empty register 1.xxx.
Use Up▲- and Down▼ keys to scroll between the faults registers.
Pressing reset key when parameter F_30 is displayed then all three fault registers will be
cleared and the display for each register will change to 1. ---, 2. ---, 3. ---.
E.g. fault log content is ‘1.OC-C’; this indicates the latest fault is OC-C, etc.
F_31
Range
Parameter Set Select
【0】: Simplified Parameter Set
【1】: Complete Parameter Set
※Note: When F_31 is set to 1 the inverter shows the Complete Parameter Set. To get back to
the Simplified Parameter Set, 13-09 has to be set to 1.
4-34