Download Operating Instructions
Transcript
F_28 Range Direct Running on Power Up 【0】: Enable Direct running after power up 【1】: Disable Direct running after power up When direct run on power up is selected by F_28 = 0 and the inverter is set to external run by F_10 = 1, if the run switch is ON as power is applied, the inverter will auto start. It is recommend that the power is turned off and the run switch is also off to avoid possibility of injury to operators and damage to machines as the power is reapplied. Note: If this mode is required all safety measures must be considered including warning labels. When direct run on power up is disabled by F_28 = 1 and if the inverter is set to external run by F_10 = 1, if the run switch is ON as power is applied, the inverter will not auto start and the display will flash with STP1. It will be necessary to turn OFF the run switch and then ON again to start normally. F_29 Range F_30 Software Version ---Fault Log Display (Latest 3 faults) Range ---Last three faults are stored in a stack and whenever there is a new fault the previous faults are pushed down the stack. So the fault stored in 2.xxx will be transferred to 3.xxx, and the one in 1.xxx to 2.xxx. The recent fault will be stored in the empty register 1.xxx. Use Up▲- and Down▼ keys to scroll between the faults registers. Pressing reset key when parameter F_30 is displayed then all three fault registers will be cleared and the display for each register will change to 1. ---, 2. ---, 3. ---. E.g. fault log content is ‘1.OC-C’; this indicates the latest fault is OC-C, etc. F_31 Range Parameter Set Select 【0】: Simplified Parameter Set 【1】: Complete Parameter Set ※Note: When F_31 is set to 1 the inverter shows the Complete Parameter Set. To get back to the Simplified Parameter Set, 13-09 has to be set to 1. 4-34