FAULT: Wrong type of unit xx-xx
Press "" to see the technical address.
FAULT: Wrong type of unit t.addr xxx
The unit is not the same type as programmed in the SSD. Change the
programming (via Win128) or the unit.
FAULT: Zone line input xx-xx
Press "" to see the technical address or the expansion board (4580)
number and input number.
FAULT: Zone line input t.addr xxx
FAULT: Zone line input x exp board x
a. Valid for the Multi purpose I/O unit 3361, connected on the COM
loop, monitored zone line input Z: Break on the zone line or wrong /
no end-of-line capacitor / short-circuit (if not programmed for fire
alarm at short-circuit).
b. Valid for the 8 zones exp. board 4580, mounted in the c.i.e.
(EBL128): Break on the zone line, wrong / no end-of-line capacitor /
short-circuit (if not programmed for fire alarm at short-circuit). .
(User programmable fault text; External fault)
A programmable input is used for an external fault to be presented in
EBL128 with a fault message.