Download Operating instructions
Transcript
Superuser/Installer – Temperature Summer/winter Operation Example: Outdoor temp (T1) > 14 °C start summer mode Summer/winter offset 2 °C 12 °C Summer/winter offset 2 °C Outdoor temp (T1) < 10 °C start winter mode Regulate deadband and temperature offset Example: Room temp > 24 °C start active cooling Room temp > 23 °C open bypass Offset for cooling 2 °C Offset for bypass 1 °C Regulation neutral zone 2 °C 20 °C Regulation neutral zone 2 °C Room temp < 18 °C start active heating or heating coil (if any) We reserve the right to make changes Page 36 of 57