Download Operating Instructions - VEGAPULS 68
Transcript
Supplement Examples of telegram configuration In the following you will see how the modules can be combined and how the appendant data telegram is structured. Example 1 (standard setting) with distance value and additional cyclical value: l l AI (PA-OUT) Additional Cyclic Value Byte-No. Format Value 1 2 3 4 IEEE-754Floating point value PA-OUT (FB1) 5 Status Status (FB1) 6 7 8 9 IEEE-754Floating point value Additional Cyclic Value 10 Status Status Example 2 with distance value without additional cyclical value: l l AI (PA-OUT) Free Place Byte-No. Format Value 1 2 3 4 IEEE-754Floating point value PA-OUT (FB1) 5 Status Status (FB1) Note: Bytes 6-10 are not used in this example. Data format of the output signal Byte4 Byte3 Byte2 Byte1 Byte0 Status Value (IEEE-754) Fig. 40: Data format of the output signal The status byte corresponds to profile 3.0 "Profibus PA Profile for Process Control Devices" coded. The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0). 66 VEGAPULS 68 - Profibus PA 29263-EN-070305 The measured value is transferred as a 32 bit floating point number in the IEEE-754 format.