Download Operating Instructions - VEGAPULS SR 68
Transcript
6 Set up with the indicating and adjustment module 4 Confirm again with [OK] and enter the actual distance from the sensor to the product surface. 5 All interfering signals in this section are detected by the sensor and stored after confirming with [OK]. Note: Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as false signal. The filling level would then no longer be detectable in this area. Further settings/Linearization curve A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level - e.g. in a horizontal cylindrical or spherical tank - and the indication or output of the volume is required. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display". Enter the requested parameters via the appropriate keys, save your settings and jump to the next menu item with the [ESC] and [->] key. If a linearisation curve is selected, the measuring signal is no longer compulsorily linear proportional to the level. This must be taken into consideration by the user, particularly when adjusting the switching point on the level switch. 42 VEGAPULS SR 68 • Profibus PA 38296-EN-110209 Caution: Note the following if the instrument with corresponding approval is used as part of an overfill protection system according to WHG: