Automatic Transfer Switch Settings
Configuring load thresholds
Web interface.
Automatic Transfer Switch
USER’S GUIDE
1 . Select the Unit tab from the navigation menu. Then select load, under
Configuration in the left navigation menu.
2 . Set the thresholds for total current or each bank. The configurable thresholds are
Overload Alarm Threshold, Near Overload Warning Threshold, and Low Load
Warning Threshold for each bank.
3 . Click Apply to save your changes or Cancel to exit without saving the changes.
Control console.
1 . From the Device Manager menu, select Load Management.
2 . Select a threshold to configure–Overload Alarm Threshold (amps), Near
Overload Warning Threshold (amps), or Low Load Warning Threshold (amps).
3 . Select Accept Changes.
Setting
Description
Overload Alarm
Threshold
Set the overload threshold, in amps, for the current drawn from
this bank during normal operation. A load at or higher than this
level generates a warning.
Near Overload
Warning Threshold
Set the number of amps at which to generate an alarm that the
Rack ATS is nearing overload of a bank.
Low Load Warning
Threshold
Set the low threshold, in amps, for the current drawn from this
bank during normal operation. A load at or below this level
generates a warning.
®
34