Download Operating Instructions VEGAPULS SR 68
Transcript
4 Mounting max. 50 mm (1.97") 1 2 3 Fig. 21: Mounting of the instrument on insulated vessels. 1 Electronics housing 2 Distance piece 3 Vessel insulation Installation in subsurface For level measurements in concrete silos, the sensors are often enclosures mounted in protective boxes. These boxes can be for example metallic, closed subsurface enclosures. 1 2 Fig. 22: Mounting of the instrument in an subsurface enclosure 38294-EN-130624 1 Subsurface enclosure 2 Concrete bottom For this application, the minimal amounts of stray radiation from the sensor can be reflected and strengthened by the walls of the subsurface enclosures. In the case of sensors with plastic housings, this can lead to coupling disturbances. This can be avoided by using a sensor with aluminium or stainless steel housing. Mounting in multiple chamber silo The silo walls of multiple chamber silos are often made of profile walls, such as e.g. profile sheeting, to ensure the required stability. If the radar sensor is mounted very close to a heavily structured vessel wall, considerable false reflections can be generated. Hence the sen- VEGAPULS SR 68 • 4 … 20 mA/HART two-wire 27