Aquatronic 1
FAULT FINDING (continued)
Problem/Symptom
Cause
Action/cure
5 Shower varies
from normal
temperature to cold
during use.
5.1 Water pressure has
dropped below
minimum required.
5.1.1 Wait until the water pressure resumes to
normal.
6 Pressure relief
device has operated
(water ejected from
PRD tube).
6.1 Blocked sprayhead.
6.1.1 Clean or replace blocked sprayplate in
sprayhead and then fit new PRD.
6.2 Twisted/blocked
flexible shower hose.
6.2.1 Check for free passage through hose.
Replace the hose if necessary and fit new PRD.
6.3 Sprayhead not
removed whilst
commissioning.
6.3.1 Fit new PRD. Commission unit with
sprayhead removed.
Note: Identify cause of operation before fitting new PRD unit.
When fitting a new PRD, follow the commissioning procedure.
It is advised all electrical maintenance/repairs to the shower
should be carried out by a suitably qualified person.
19