Download INSTALLATION MANUAL
Transcript
4. Individual start/stop (ON/OFF) individual test operation function This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same system by using switches on the interface board of the outdoor unit. Set SW01 [16] and set SW02 and SW03 to indoor address No. (1 to 64) to be started (Refer to the following table*) - only the setup indoor unit starts operation. (In the rotary switches of the indoor unit which operates in a group by the remote controller, the follower indoor unit cannot be individually started or stopped. In this case, [ --] is displayed on 7-segment display [B] on the interface P.C. board of the outdoor unit.) <Operation procedure> Power ON Be sure to turn on power at the outdoor side after power-ON of indoor unit. If an error is already displayed under condition of SW01 [1], SW02 [1], SW03 [1], return the status to normal one according to troubleshooting and then execute a test operation. The unit which is not given with priority by heating priority control, cooling priority control, and selection of cooling or heating mode is not operated. In this case, [ ] or [ ] is displayed on the remote controller. Set up the operation mode of the remote controller. (If it is not set up, the operation starts with the current mode.) Interface P.C. board 7-segment display [A] SW04 Match the rotary switch on the interface P.C. board of the outdoor unit * with in the following table. 7-segment display [B] SW05 (7-segment display) [A] [ [B] ] Address display of corresponding indoor unit [ ] [ 00] is displayed for 5 seconds after operation-ON. SW01 SW02 SW03 <Rotary switch> (7-segment display) Push the push-switch SW04 on the interface [A] [B] P.C. board of the outdoor unit for 2 seconds or more. [ ] [ ] (If pushing this switch continuously for 10 seconds or more, the operation changes to the individual Address display of [ 11] is displayed for test operation.) corresponding indoor unit 5 seconds after operation-ON. (For individual test operation,[ FF] is displayed.) Start The indoor unit to be started operates. * Push the push-switch SW05 on the interface P.C. board of the outdoor unit for 2 seconds or more. SW01 SW02 SW03 16 1 to 16 1 Address 1 to Address 16 16 1 to 16 2 Address 17 to Address 32 16 1 to 16 3 Address 33 to Address 48 16 1 to 16 4 Address 49 to Address 64 (7-segment display) [A] [ [B] ] Address display of corresponding indoor unit [ Units to be operated ] [ 00] is displayed for 5 seconds after operation-ON. After test operation, return the display select switches SW01, SW02, and SW03 on the interface P.C. board of the outdoor unit to [1], [1], [1] respectively. End NOTE) The individual test operation returns to the normal operation after 60 minutes. 166 } } } } individually individually individually individually In individual start/stop