DCREG2
DCREG4
7.1.15
15P0059B3
USER
MANUAL
M014: M AIN A NALOG I NPUT
M014 TermRef
TermRef ***** %
7.1.16
AND
7
P M014 - TermRef
R -100 ... 100. %
F This parameter indicates, as a percentage of the max. reference corresponding
to 10V, the value of the reference resulting from the application of the REF main
analog input between terminals 5 and 7. The reference obtained is either a
speed / voltage reference or a current reference if the 6:Slave function is entered
through a digital input (see par. C130 … C135).
The value per cent displayed in this parameter, either as a speed / voltage
reference or a current reference, considers the Gain, Bias and Polarity blocks
(see par. P122, P121 and P120, or par. P125, P124 and P123 respectively for
the two types of references) applied in the above-mentioned order.
For example, if a motor rotates at 2000 RPM with a 10V reference and if P122 =
100%, then with a 10V reference and if P122 = 25% the motor will rotate at 500
RPM (the display will show M014 = 25% and M001 = 25%); otherwise, with a
2.5V reference and if P122 = 200%, the motor will rotate at 1000 RPM (the
display will show M014 = 50% and M001 = 50%).
The value per cent displayed in this parameter also indicates the reference
obtained from a current external signal (milliAmpere) if jumper JP7 in ES801
(JP407 in ES906) is set in pos. 2-3: if the user intends to use an analog input as
a 0(4) … 20mA signal, the value to program in the parameters relating to the
Gain and Bias operators is stated in the INPUT / OUTPUT SIGNAL IN
MILLIAMPERE chapter.
P M015 - SLRef
R -100. ... 100. %
F This parameter indicates, as a percentage of the max. value corresponding to
10V, the value of the reference applied through serial connection.
M016: F IELD B US R EFERENCE
M016 FBusRef
FBRef ***** %
7.1.18
T ERMINALS 5
M015: S ERIAL C ONNECTION R EFERENCE
M015 SLinkRef
SLRef ***** %
7.1.17
TO
P M016 - FBRef
R -100. ... 100. %
F This parameter indicates, as a percentage of the max. value corresponding to
10V, the value of the reference applied through the field bus.
M017: F IELD C URRENT R EFERENCE
M017 FldCurrRef
RefFld **** %
P M017 - RefFld
R 0.00 ... 100. %
F It indicates, as a percentage of the max. reference corresponding to the max.
field current that may be generated by the drive, the current loop input
(corresponding to the voltage loop output) of the internal field regulator. The
standard values of the max. field current generated by the drive are equal to 5A
for DCREG.100max, 15A for DCREG.150min Size 1, and 35A for DCREG Size
2(A) and MODULAR.S.
For instance, for a DCREG.350, 100% of M017 will correspond to 15A.