Download DCREG2 DCREG4 USER MANUAL
Transcript
DCREG2 DCREG4 7.1.15 15P0059B3 USER MANUAL M014: M AIN A NALOG I NPUT M014 TermRef TermRef ***** % 7.1.16 AND 7 P M014 - TermRef R -100 ... 100. % F This parameter indicates, as a percentage of the max. reference corresponding to 10V, the value of the reference resulting from the application of the REF main analog input between terminals 5 and 7. The reference obtained is either a speed / voltage reference or a current reference if the 6:Slave function is entered through a digital input (see par. C130 … C135). The value per cent displayed in this parameter, either as a speed / voltage reference or a current reference, considers the Gain, Bias and Polarity blocks (see par. P122, P121 and P120, or par. P125, P124 and P123 respectively for the two types of references) applied in the above-mentioned order. For example, if a motor rotates at 2000 RPM with a 10V reference and if P122 = 100%, then with a 10V reference and if P122 = 25% the motor will rotate at 500 RPM (the display will show M014 = 25% and M001 = 25%); otherwise, with a 2.5V reference and if P122 = 200%, the motor will rotate at 1000 RPM (the display will show M014 = 50% and M001 = 50%). The value per cent displayed in this parameter also indicates the reference obtained from a current external signal (milliAmpere) if jumper JP7 in ES801 (JP407 in ES906) is set in pos. 2-3: if the user intends to use an analog input as a 0(4) … 20mA signal, the value to program in the parameters relating to the Gain and Bias operators is stated in the INPUT / OUTPUT SIGNAL IN MILLIAMPERE chapter. P M015 - SLRef R -100. ... 100. % F This parameter indicates, as a percentage of the max. value corresponding to 10V, the value of the reference applied through serial connection. M016: F IELD B US R EFERENCE M016 FBusRef FBRef ***** % 7.1.18 T ERMINALS 5 M015: S ERIAL C ONNECTION R EFERENCE M015 SLinkRef SLRef ***** % 7.1.17 TO P M016 - FBRef R -100. ... 100. % F This parameter indicates, as a percentage of the max. value corresponding to 10V, the value of the reference applied through the field bus. M017: F IELD C URRENT R EFERENCE M017 FldCurrRef RefFld **** % P M017 - RefFld R 0.00 ... 100. % F It indicates, as a percentage of the max. reference corresponding to the max. field current that may be generated by the drive, the current loop input (corresponding to the voltage loop output) of the internal field regulator. The standard values of the max. field current generated by the drive are equal to 5A for DCREG.100max, 15A for DCREG.150min Size 1, and 35A for DCREG Size 2(A) and MODULAR.S. For instance, for a DCREG.350, 100% of M017 will correspond to 15A. 117/192