Download User's Manual (Hardware)
Transcript
(3) Fail-safe measures against failure of the PLC Failure of a CPU module or memory can be detected by the self-diagnosis function. However, failure of I/O control area may not be detected by the CPU module. In such cases, all I/O points turn ON or OFF depending on a condition of problem, and normal operating conditions and operating safety cannot sometimes be maintained. Though Mitsubishi PLCs are manufactured under strict quality control, they may cause failure or abnormal operations due to unspecific reasons. To prevent the abnormal operation of the whole system, machine breakdown, and accidents, fail-safe circuitry against failure of the PLC must be constructed outside the PLC. Examples of a system and its fail-safe circuitry are described below: <System example> Input Input Input Input Output Power CPU 16 16 16 16 16 supply module points points points points points module Output Power Output Output Output 16 16 16 points Vacant supply 16 Y80 module points points points Y8F Output module for fail-safe purpose*1 *1: The output module for fail-safe purpose should be loaded in the last slot of the system. (Y80 to Y8F in the above system.) <Fail-safe circuit example> ON delay timer Internal program Y80 T1 1s OFF delay timer SM412 Y80 Y80 T2 Y81 External load L Y8F L 1s MC 24V 0.5s 0.5s - + 0V CPU module 24VDC Output module *2 T1 T2 MC *2: Y80 repeats turning ON and then OFF at 0.5 second intervals. Use a no-contact output module (transistor in the example shown above). 46