Download TECHNICAL & SERVICE MANUAL
Transcript
From the previous page. Display Abnormal point and detecting method 6607 Causes 2) When synchronized operation with lossnay in other refrigerant system, the indoor units transmit the signal to the lossnay after the lossnay and same refrigerant system outdoor unit are turned off or turned on again in 2 minutes, and detects abnormality. Check points 3) Contact failure of lossnay or indoor unit transmission cable. 4) Indoor unit transmission connector (CN2M) disconnection. 5) Sending/receiving signal circuit failure in the indoor unit or lossnay. 6) When the controller of displayed address and attribute is not recognized 1) Since the address switch was changed with the current passed, the unit in the last address does not exist. 2) Since the fresh master/ lossnay address are changed after synchronized setting of fresh master/ lossnay by the remote controller, abnormality is detected at transmitting from the indoor unit. 6608 No response Though there was a reply (ACK) of having received signal from the other side, it is the abnormality when the response command does not return. The sending side detects the abnormality continuously 6 times every 30 seconds. Note) Address/Attribute displayed on the remote controller shows the controller, which did not response. 1) Transmission repeats the failure by the noise etc. Check the transmission wave and noise on the transmission cable. Turn off power supply of outdoor unit, 2) Decline of transmission voltage and indoor unit and lossnay for 2 minutes signal by transmission cable tolerance or more at the same time. Then, turn over. on power supply again. It recovers · The furthest point···200m normally at the malfunction that · Remote controller cable···(12m) happens by chance. When same (Refer to 8-3.) abnormality occurs again, it is defective of displayed address and attribute. 3) Decline of transmission line voltage and signal by unmatched kind of cable. · Shield wire-CVVS,CPEVS wire diameter···1.25Aor more 4) Mis-operation of origin controller, which happens by chance. 49