Download Service Manual - Daikintech.co.uk
Transcript
Outline of Control (Outdoor Unit) < Symbols using in this manual > SiE33-105 3.5.2 Low Pressure Protection Control The following control is provided to protect the compressors from abnormal decrease of low pressure (LP). [Cooling mode] OR LP<0.15MPa OR •& Compressor operation frequency 31Hz+OFF+OFF Normal operation •& •& • LP>0.20MPa • 30 sec elapse • Ta<Tes+5 • LP<0.08MPa • Ta>5˚C • LP<0.049MPa • Ta≤5˚C SVP (for hot gas bypass) : ON Ta : Outdoor air temp. (˚C) Tes : Low pressure equivalent saturation temp. (˚C) • LP>0.13MPa • & • Ta>5˚C OR • LP<0.098MPa •& • Ta≤5˚C [Heating mode] LP<0.08MPa Normal operation SVP : OFF 0 LP<0.05MPa SVP (for hot gas bypass) : ON LP<0.03MPa Restriction for upper limit compressor operation frequency 1 0 Forced thermostat OFF LP>0.10MPa (Monitoring LP every 30 sec.) LP>0.07MPa (Monitoring LP every 1 min) LP > 0.13 MPa Upper limit frequency = Maximum frequency LP<0.0MPa E4 malfunction stop 0 Malfunction reset LP>0.09MPa 1-step increase for compressor operation frequency [Oil return mode (common for cooling / heating)] LP<0.05MPa SVP (for hot gas bypass) : OFF SVP (for hot gas bypass) : ON LP>0.10MPa (V0822) 1.Upper limit compressor operation : According to “Drooping step Table”. See next page. 74 Function R-407C PLUS Series Heat Recovery System