Download 2711-6.0.4, DeviceNet User Guide
Transcript
3 DeviceNet PanelView Terminals DeviceNet terminals have a 10 at the end of their catalog number, for example 2711-K9A10. DeviceNet terminals have • DeviceNet communications port • RS-232 port Making DeviceNet Connections Use one of the cables below to connect the DeviceNet version of the PanelView terminal to a DeviceNet network. Cable Catalog No. DeviceNet Cable, 50 meters (164 feet) 1485C-P1A50 DeviceNet Cable, 100 meters (328 feet) 1485C-P1A150 DeviceNet Cable, 150 meters (492 feet) 1485C-P1A300 Important: Refer to DeviceNet Cable System Planning and Installation manual (Publication 1485-6.7.1) for network layout and design information. DeviceNet Connector The DeviceNet connector is identified by the label on the PanelView terminal. PanelView 900 shown 5 1 DeviceNet Port DeviceNet Terminal Block Terminal Signal Function Color 1 COM Common Black 2 CAN_L Signal Low Blue 3 SHIELD Shield Uninsulated 4 CAN_H Signal High White 5 VDC+ Power Supply Red 1 5 The typical DeviceNet current draw is 90 mA at 24V per terminal. Publication 2711-6.0.4