Download 2711-6.0.4, DeviceNet User Guide
Transcript
8 Configuring DeviceNet Communications DeviceNet communication parameters are accessed from the Terminal Setup dialog. To open the Terminal Setup dialog, select Application>Terminal Setup. 1. Click the Comms. Setup button from the Terminal Setup dialog. 2. Under Terminal, edit the following parameters. Specify To: Node Address Select the address (0 to 63) of the PanelView terminal on the DeviceNet link. Baud Rate Select the baud rate of the DeviceNet link. The available baud rates are 125 kbps, 250 kbps, 500 kbps. 3. Under I/O Scanner, edit the following parameters: Publication 2711-6.0.4 Specify To: Input Size Specify the number of words (0 to 64) that are sent to the scanner from the PanelView with each I/O message. 0 is the default value which indicates that no input I/O data exists in the application. Size must match configuration in Master device. Output Size Specify the number of words (0 to 64) that are received by the PanelView from the scanner with each I/O message. 0 is the default value which indicates that no output I/O data exists in the application. Size must match configuration in Master device.