Download Operating Instructions
Transcript
Settings in the "reduced menu" 6.3 Adjustment without medium TAGNo. 1 % xx,x Adjustment example You know the data of the sensor, i.e. you know that at 0 % filling the sensor delivers a current of 4.2 mA and at 100 % filling a current of 15.5 mA. Enter these values in the menu items. Meas. value indication Param. TAGNo. 1 15.5 mA at 100 % Adjustment with medium without medium 0% at mA 4,000 100% at mA 20,000 4.2 mA at 0 % For this adjustment procedure you have to enter two sensor current values (4 … 20 mA) corresponding to the levels 0 % and 100 %. 0% at mA 4,200 100% at mA 15,500 Enter in these two menu items the values of the senor. Use the [+] and [–] keys to set the values and [OK] to save the values. VEGAMET 514 21